2021-12-16 15:43:57 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-19051525 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS NEW SCOPE OF WORK HAS INCREASED THE VALUE OF |
| THE ORIGINAL PROJECT. PLEASE SUBMIT A NEW PLAN REVIEW |
| REQUEST FORM SHOWING THE NEW REVISED VALUE OF THIS |
| PROJECT. FBC 107.2.1 |
| |
| 2) NOTHING ABOUT THE HOOD OR THE REFRIGERATION WILL BE |
| REVIEWED UNDER THIS PERMIT. A SEPARATE PERMIT FOR EACH |
| WILL BE REQUIRED. |
| |
| 3) SHEET M1.03: THE MEASUREMENT FROM THE HOOD EXHAUST |
| TERMINATION TO THE MUA INTAKE IS SHOWING A MEASUREMENT |
| OF 8 FT 7 INCHES, PLEASE SHOW THIS CLEARANCE MEETS THE |
| 10 FEET MINIMUM. FBC M 401.4 |
| |
| 4) PLEASE SHOW THE RETURN AIR PATH FROM THE KITCHEN TO |
| AHU-3. FBC M 601.6 |
| |
| 5) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR THE MECHANICAL SYSTEMS. FBC EC |
| C403.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |