2019-12-30 08:30:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19051525
 12/30/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 317A & M1.03: BASED ON THE DRAWINGS IT
 APPEARS THE NEW SCREENING ON THE ROOF WILL ALSO
 FUNCTION AS THE REQUIRED GUARD AT THE ROOF EDGES, AND
 SHALL BE IN COMPLIANCE WITH SECTION 1607.8.1 FBC B
 HANDRAILS AND GUARDS.
  
 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) (0.73
 KN/M) IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS
 HANDRAIL ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH
 SECTION 2407.
  
 PLEASE VERIFY THE SCREENING WILL BE IN COMPLIANCE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  