Plan Review Notes For Permit 19051525 |
Permit Number |
19051525 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-04-19 14:04:12 | 2ND REVIEW FBC-2020 FUEL GAS | | PERMIT-19051525 | | 4/19/22 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST | | REVIEW PRINTED BELOW WAS NOT ADDRESSED. PLEASE PROVIDE | | THE SUBMITTALS OR INDICATE THEY WILL BE DEFERRED PER | | SEC 107.4.1 WPB. | | | | 2) P301: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | COOKING APPLIANCES MARKED OR HIGHLIGHTED TO SHOW THE | | BTU LOADS AND THE INPUT PRESSURES- SEC. 623.1 FBC FG. | | PLEASE NOTE THAT REGULATORS MAY BE REQUIRED AT EACH | | APPLIANCE BASED ON INPUT PRESSURE RATINGS- SECTION | | 410.2 FBC FG. PLEASE REVIEW THE SPECS AND SHOW | | REGULATORS AND INPUT/OUTPUT PRESSURES WHERE REQUIRED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|