Plan Review Notes For Permit 19051525 |
Permit Number |
19051525 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-12-16 13:20:55 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THE RECONSTURCTION OF THE ROOF SYSTEM INDICATES | | LIGHT-FRAMET TRUSS TYPE. | | | | | | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR | | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. | | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT | | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES | | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE | | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A | | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND | | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. | | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO | | THE LEFT OF THE MAIN ENTRY DOOR. | | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | MARKED WITH THE LETTER "R". | | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | SHALL BE MARKED WITH THE LETTER "F". | | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|