Plan Review Notes
Plan Review Notes For Permit 19051525
Permit Number 19051525
Review Stop B
Sequence Number 2
Notes
Date Text
2020-01-06 13:28:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN.6TH/2020
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) SHEET G DRAWING INDEX & PROJECT INFO:
  
 1A)(1) PLEASE CORRECT THE SHEET G THE DRAWING INDEX
 WITH SURVEY SHEET LISTED 005G AS SHOWN IN THE INDEX OR
 REMOVE THE SHEET NUMBER WITH A REVISION.
 1ST ROUND OF COMMENTS. PLEASE NOTE THE DRAWING INDEX
 THERE SHOULD BE A SURVEY SHEET 005G BETWEEN SHEET 004 G
 STANDARD ABBREVIATIONS & SYMBOLS SHEET AND CIVIL COVER
 SHEET 100C. MISSING DOCUMENT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1A)(2) NEW COMMENT. A SURVEY IS REQUIRED TO DETERMINE
 THE EXISTING BUILDING AND LOCATION OF LOT LINES, ALL
 LOT LINES, NOT JUST THE ADJOINING LOT 713. THERE ARE
 MANY REQUIREMENTS THAT WILL NEED TO SEE HOW FAR THE
 BUILDING IS FROM THE PROPERTY LINE. EXTERIOR FIRE
 RATING OF WALLS, REAR EGRESS FROM THE BUILDING AND
 CANOPY, EGRESS COURT REQUIREMENTS, THESE AND OTHER
 REQUIREMENTS CANNOT BE DETERMINED UNTIL A SURVEY IS
 SUBMITTED SHOWING THE DISTANCE FROM THE BUILDING TO THE
 PROPERTY LINE IN ALL DIRECTIONS. PLEASE NOTE THE SURVEY
 SUBMITTED SHEET 103 ENGINEERING PLAN IS FOR
 TOPOGRAPHICAL USE AND SANITARY USE ONLY. NOTE THIS
 SURVEY ALSO INDICATES THE PROPERTY AS ONE LARGE LOT NOT
 2 ADJOINING LOTS WHICH IS INCORRECT. THE SURVEY BY ENG
 ENUITY GROUP INC. HAS AN ELECTRONIC SIGNATURE AND SEAL
 12/11/2019 BY ADAM SWANEY. APPARENTLY THE SHEET WAS
 PRINTED ON A PAPER COPY WAS UPLOADED, THERE IS NO
 ELECTRONIC SIGNATURE NOR SEAL ON THIS SHEET
 OR THERE WAS NEVER A ELECTRONIC SIGNATURE & SEAL.
  
 1B) THIS REVIEW WILL NEED TO BE FAILED SINCE THERE IS
 NO UNITY OF TITLE FILED WITH THE CLERK OF THE COURTS
 OFFICE. THE REQUEST TO HAVE THE UNITY OF TITLE AFTER
 THE PERMIT IS ISSUED WILL NEED TO BE DECIDED ON BY THE
 BUILDING OFFICIAL ROBERT BROWN AND THE DIRECTOR OF THE
 CRA, STIPULATIONS WILL ALSO NEED TO BE AGREED UPON AND
 BEFORE THE ISSUANCE OF A CERTIFICATE OF COMPLETION
 SINCE THIS PERMIT IS FOR A SHELL ONLY.
  
 1ST ROUND OF COMMENTS. WHEN VIEWING THIS PROJECT IN THE
 PALM BEACH COUNTY PROPERTY APPRAISERS WEBSITE THE
 PROJECT COMPRISES OF 2 LOTS 719 AND 713 N. SAPODILLA
 AVE. PLEASE NOTE WITHOUT A UNITY OF TITLE THE CANOPY
 CANNOT BE BUILT SINCE IT PASSES OVER PROPERTY LINES OF
 2 ADJOINING LOTS.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 OR
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1C) COMPLIED. NO HISTORIC EXEMPTIONS ARE BEING TAKEN.
  
 1D) 2ND ROUND OF COMMENTS. USING THE SHEET 103C
 ENGINEERING PLAN THE DESIGNER OF RECORD DOES SHOW UNDER
 THE PROPOSED OUTDOOR COVERED PATIO THE 2 REQUIRED
 EXITS. THERE IS ONLY 1 EXIT WHICH IS AN ACCESSIBLE
 EXIT. AS NOTED IN THE 1ST REVIEW IF 2 EXITS ARE
 REQUIRED, THEN 2 ACCESSIBLE EXITS TO THE PUBLIC WAY
 WOULD BE REQUIRED. THE 2ND MEANS OF EGRESS DROPS YOU
 OFF BEHIND THE COVERED PATIO INTO A GRASSED AREA. THIS
 MEANS OF EGRESS NEEDS TO BE EXTENDED TO THE PUBLIC WAY.
 THE 2ND ISSUE WITH THIS MEANS OF EGRESS, A SURVEY WITH
 MEASUREMENTS FROM THE BUILDING ARE NOT SHOWN. IS THERE
 AN ALLEY BEHIND THIS LOT OR ANOTHER LOT? IT CANNOT BE
 DETERMINED IF THE EXIT DISCHARGE FROM UNDER THE COVERED
 OUTDOOR PATIO TO THE PROPERTY LINE FOR THE EGRESS COURT
 WILL REQUIRE 1 HOUR RATED WALLS AT THE PROPERTY LINE,
 SEE 2017 FBC-B SECTION 1028.4.2.
  
 1ST ROUND OF COMMENTS. PLEASE NOTE THE TABLE SHOWING
 THE OCCUPANT LOAD FOR THE BUILDING AS A TOTAL 145
 OCCUPANTS. PLEASE NOTE THAT THE COVERED OUTDOOR PATIO
 IS ALREADY OUTSIDE OF THE BUILDING AND A SEPARATE COUNT
 SHOULD BE TAKEN FOR THIS OUTDOOR SEATING. A SEPARATE
 PERMIT SHOULD BE APPLIED FOR THE CANOPY. PLEASE ALSO
 NOTE THE OCCUPANT LOAD UNDER THE OUTDOOR CANOPY IS
 STATED AT 77 REQUIRING 2 EXITS.
 PLEASE NOTE THE CURRENT EXIT FROM THE PATIO EXITS ONTO
 THE GRASS, NOT AN ACCESSIBLE EXIT. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
  
 1E) COMPLIED.
  
 2) LIFE SAFETY SHEET LS1:
  
 2A)(1) SEMI-COMPLIED SEE COMMENT (1D), REQUIRES 2
 ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY.
 1ST ROUND OF COMMENTS. WITHIN THE BUILDING THE PLANS
 SHOW 2 REQUIRED EXITS. UNDER THE COVERED OUTDOOR PATIO
 THE WITH AN OCCUPANT LOAD OF 77 BUT ONLY ONE MEANS OF
 EGRESS, YOU CAN?T REENTER THE BUILDING FOR THE 2ND
 MEANS OF EGRESS, PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B TABLE 1006.2.1 MAXIMUM OCCUPANT LOAD WITH ONE
 EXIT.
  
 2A)(2) NEW COMMENT. SHEET 002 PROJECT INFO STATES THERE
 IS 90 SEATS ON THE EXTERIOR PATIO, THE LIFE SAFETY
 SHEET 1ST FLOOR INDICATES 100 SEATS WHEN YOU COUNT THE
 SEATS 110 SEATS ON THE PATIO. WHERE THE 2 PATIO EXITS
 ARE IN A GREY BOX AND STATING FUTURE ASSEMBLY
 CONCENTRATED, THIS AREA IS PART OF THE EGRESS PATH AND
 NOT HAVE OCCUPANTS BLOCKING THE EGRESS PATH. PLEASE
 REVIEW: WHERE PERSONS ARE ADMITTED TO THE BUILDING AT
 TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL
 BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE,
 PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH
 UPON THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE
 MEANS OF EGRESS. 2017 FBC-B 1029.4.
  
 2B) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE
 OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON
 SHEETS 315A, 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR
 CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS
 TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE
 PLANS INDICATE UNDER SEPARATE PERMIT.
 1ST ROUND OF COMMENTS. IS THE COVERED OUTDOOR PERMIT
 SUPPOSED TO BE PART OF THIS PERMIT PACKAGE OR UNDER A
 SEPARATE PACKAGE. THERE IS NO DESIGN INFORMATION FOR
 THIS PORTION OF WORK. IS THE SAME CONTRACTOR FOR THE
 BUILDING AS THE COVERED OUTDOOR DINING AREA. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 2C) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE
 OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON
 SHEETS 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR
 CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS
 TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE
 PLANS INDICATE UNDER SEPARATE PERMIT.
 1ST ROUND OF COMMENTS. THE COVERED OUTDOOR DINING AREA.
 THERE IS NO INFORMATION FOR THIS AREA OF WORK. WILL
 THERE BE PLASTIC WIND BREAKS ADDED TO THE CANOPY FOR
 RAIN AND HEAT IN THE WINTER? 107.2.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 2D) COMPLIED. MEZZANINE LEVEL IS 1/3RD THE FLOOR AREA
 ALLOWED BY SECTION 505.2.1
  
 2E) 2ND REQUEST. THE PLANS LIFE SAFETY 1ST FLOOR AND
 MEZZANINE LEVEL STATE YES FIRE EXTINGUISHERS ON THE
 PLAN BUT DO NOT PLACE THEM IN THE BUILDING SHOWING CODE
 COMPLIANCE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1ST ROUND OF COMMENTS. THE PLANS UNDER THE HEADING OF
 FIRE PROTECTION SYSTEMS ALSO INDICATES PORTABLE FIRE
 EXTINGUISHERS BUT NONE ARE SHOWN ON THE FLOOR PLAN OR
 COMPLIANCE WITH 2017 FBC-B 906.1.
  
 2F) NEW COMMENT. THE 1ST FLOOR LIFE SAFETY PLAN SHOWS 1
 ACCESSIBLE SEAT AT WHAT APPEARS TO BE THE BAR, PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBLITY CODE
 SECTION. 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2G) NEW COMMENT. THE 1ST FLOOR PLAN HAS A TOTAL OF 153
 SEATS ON THE 1ST FLOOR. 153 XO.O5= 7.65 OR 8 ACCESSIBLE
 SEATS REQUIRED. THE PLAN ONLY SHOWS 6 PLEASE UPDATE THE
 PLANS. 2017 ACCESSIBILITY CODE 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 3) SHEET LS 2 THE MEZZANINE PLAN.
  
 3A-B) COMPLIED.
  
 4) COMPLIED. ROOF HATCH 16 SQ. FT. OF OPENING.
  
 5-7) COMPLIED.
  
 8) 2ND REQUEST. PERMIT 19051529 IF THIS PERMIT IS FOR
 THE SCREENING PROPERTY LINE WALL OR IS IT FOR SCREENING
 WALL ON THE ROOF TOP FOR THE A/C UNITS. THE RESPONSE
 COMMENTS SOUND AS IF IT IS FOR THE ROOF TOP SCREENING
 OF THE A/C EQUIPMENT WHICH WOULD BE PART OF THE MAIN
 BUILDING PERMIT? A SEPARATE PERMIT IS REQUIRED FOR PLAN
 SHEET A326 TRASH ENCLOSURE AND PRECAST CONCRETE WALL
 SYSTEM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) PROVISO: SHEET 328 A ROOF DETAILS, DETAIL 3. 2017
 FBC-B TABLE 1510.10. BOTTOM OF HORIZONTAL FRAMING
 MEMBER ALLOWS FOR THE WIDTH OF THE A/C UNIT TO BE 24
 -36 INCHES WIDE.
  
 10) COMPLIED.
  
 11) COMPLIED, ASCE 7-10.
  
 12) 2ND REQUEST. SHEET 400S. S1 UNDER THE HEADING OF
 SHALLOW FOUNDATION MENTIONS A SOILS REPORT BY
 GEOTECHNICAL MATERIAL TESTING INSPECTION SERVICES DATED
 01/18/2018, PLEASE SUBMIT THE REPORT FOR ITS FINDINGS.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 PLEASE SUBMIT EITHER IF IN PAPER AN ORIGINAL SIGNED AND
 SEALED REPORT. IF ELECTRONICALLY THE REPORT WILL NEED
 TO BE SIGNED AND SEALED ELECTRONICALLY.
  
 13) PROVISO: THIS PROJECT HAS BOLTED STEEL CONNECTIONS
 AS WELL AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 14) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 15A) PROVISO/ DEFERRED SUBMITTALS. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15B) PROVISO/ DEFERRED SUBMITTALS. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 15C)PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) PROVISO/ DEFERRED SUBMITTALS. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 17A) PROVISO/ DEFERRED SUBMITTALS. ROOFING PRODUCT
 APPROVALS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 17B) PROVISO/ DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 18) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  