Plan Review Notes
Plan Review Notes For Permit 19051525
Permit Number 19051525
Review Stop G
Sequence Number 1
Notes
Date Text
2021-12-17 11:18:091ST REVIEW FBC-2020 FUEL GAS
 PERMIT-19051525
 12/16/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P301: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 2) P301: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 COOKING APPLIANCES MARKED OR HIGHLIGHTED TO SHOW THE
 BTU LOADS AND THE INPUT PRESSURES- SEC. 623.1 FBC FG.
 PLEASE NOTE THAT REGULATORS MAY BE REQUIRED AT EACH
 APPLIANCE BASED ON INPUT PRESSURE RATINGS- SECTION
 410.2 FBC FG. PLEASE REVIEW THE SPECS AND SHOW
 REGULATORS AND INPUT/OUTPUT PRESSURES WHERE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  