Plan Review Notes
Plan Review Notes For Permit 19051525
Permit Number 19051525
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-23 07:49:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JULY 22/2019
 ACTION: DENIED
  
 1) SHEET G DRAWING INDEX & PROJECT INFO:
  
 1A) PLEASE NOTE THE DRAWING INDEX THERE SHOULD BE A
 SURVEY SHEET 005G BETWEEN SHEET 004 G STANDARD
 ABBREVIATIONS & SYMBOLS SHEET AND CIVIL COVER SHEET
 100C. MISSING DOCUMENT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) WHEN VIEWING THIS PROJECT IN THE PALM BEACH COUNTY
 PROPERTY APPRAISERS WEBSITE THE PROJECT COMPRISES OF 2
 LOTS 719 AND 713 N. SAPODILLA AVE. PLEASE NOTE WITHOUT
 A UNITY OF TITLE THE CANOPY CANNOT BE BUILT SINCE IT
 PASSES OVER PROPERTY LINES OF 2 ADJOINING LOTS.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE. / UNITY OF CONTROL (2) DIFFERENT
 OWNERS/ QUICK CLAIM DEED
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 OR
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1C) UNDER THE SCOPE OF WORK THE PLANS STATE THAT THIS
 PROJECT IS THE RECONSTRUCTION OF A HISTORIC BUILDING,
 BUT THERE IS NO EXPLANATION AS TO WHAT EXEMPTIONS YOU
 ARE TAKING FOR A HISTORIC BUILDING. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) PLEASE NOTE THE TABLE SHOWING THE OCCUPANT LOAD FOR
 THE BUILDING AS A TOTAL 145 OCCUPANTS. PLEASE NOTE THAT
 THE COVERED OUTDOOR PATIO IS ALREADY OUTSIDE OF THE
 BUILDING AND A SEPARATE COUNT SHOULD BE TAKEN FOR THIS
 OUTDOOR SEATING. A SEPARATE PERMIT SHOULD BE APPLIED
 FOR THE CANOPY. PLEASE ALSO NOTE THE OCCUPANT LOAD
 UNDER THE OUTDOOR CANOPY IS STATED AT 77 REQUIRING 2
 EXITS.
 PLEASE NOTE THE CURRENT EXIT FROM THE PATIO EXITS ONTO
 THE GRASS, NOT AN ACCESSIBLE EXIT. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 1E) SHEET 002 G THE DRAWING INDEX & PROJECT INFO SHEET
 UNDER THE HEADING OF FIRE PROTECTION THE PLAN INDICATES
 NO FIRE SPRINKLERS FOR THIS PROJECT WHEREAS ON SHEET
 404S-S2.2 THE ROOF FRAMING PLAN ROOF NOTE 2 INDICATES
 THE JOIST DELEGATE ENGINEER SHALL COORDINATE W/ FIRE
 SPRINKLER PLAN FOR THE SPRINKLER LOCATIONS AND LOADS TO
 BE SUPPORTED BY THE JOIST. DISCREPANCY IN PLANS.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) LIFE SAFETY SHEET LS1:
 2A) WITHIN THE BUILDING THE PLANS SHOW 2 REQUIRED
 EXITS. UNDER THE COVERED OUTDOOR PATIO THE WITH AN
 OCCUPANT LOAD OF 77 BUT ONLY ONE MEANS OF EGRESS, YOU
 CAN?T REENTER THE BUILDING FOR THE 2ND MEANS OF EGRESS,
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B TABLE
 1006.2.1 MAXIMUM OCCUPANT LOAD WITH ONE EXIT.
  
 2B) IS THE COVERED OUTDOOR PERMIT SUPPOSED TO BE PART
 OF THIS PERMIT PACKAGE OR UNDER A SEPARATE PACKAGE.
 THERE IS NO DESIGN INFORMATION FOR THIS PORTION OF
 WORK. IS THE SAME CONTRACTOR FOR THE BUILDING AS THE
 COVERED OUTDOOR DINING AREA. 107.2.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 2C) THE COVERED OUTDOOR DINING AREA. THERE IS NO
 INFORMATION FOR THIS AREA OF WORK. WILL THERE BE
 PLASTIC WIND BREAKS ADDED TO THE CANOPY FOR RAIN AND
 HEAT IN THE WINTER? 107.2.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 2D) FIRST FLOOR COMMERCIAL KITCHEN AND LEASE SPACE
 INSIDE WALL LINE IS APPROXIMATELY 1,328.5 SQ. FT. IT
 APPEARS THE MEZZANINE LEVEL IS OVER THE ALLOWABLE 1/3RD
 THE FLOOR AREA ALLOWED BY SECTION 505.2.1 AREA
 LIMITATION OF THE 2017 FBC-B. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT
 GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM
 OR SPACE IN WHICH THEY ARE LOCATED. THE ENCLOSED
 PORTION OF A ROOM SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED.
 THE 1,362.5 SQ. FT. AREA OF THE 1ST FLOOR MINUS 118 SQ.
 FT. (RESTROOMS) OR 1,244.5/ 3 = 414.66 ALLOWABLE AREA
 FOR THE MEZZANINE. THE AREA OF THE MEZZANINE WALLS
 INCLUDED IS APPROX. 492 SQ. FT. OR 78 SQ. FT. OVER THE
 ALLOWABLE AREA. THERE IS ALSO AN AREA OF CONCERN WHAT
 APPEARS TO BE JANITORS CLOSET THAT WAS NOT INCLUDED IN
 THE REDUCTION FACTOR.
  
 2E) THE PLANS UNDER THE HEADING OF FIRE PROTECTION
 SYSTEMS ALSO INDICATES PORTABLE FIRE EXTINGUISHERS BUT
 NONE ARE SHOWN ON THE FLOOR PLAN OR COMPLIANCE WITH
 2017 FBC-B 906.1.
  
 3) SHEET LS 2 THE 2ND FLOOR (MEZZANINE) PLAN.
  
 3A) THIS PLAN SHOWS AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OF 30 OCCUPANTS. PLEASE PROVIDE
 COMPLIANCE WITH THE 2017 EXISTING BUILDING CODE SECTION
 1006.1. ACCESSIBILITY IN PORTIONS OF THE BUILDING
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE:
 FBC- ACCESSIBILITY CODE 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 SEE ACCESSIBILITY CODE SECTION 408.1.
 LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL COMPLY
 WITH 408 AND WITH ASME A17. THEY SHALL BE PASSENGER
 ELEVATORS AS CLASSIFIED BY ASME A17.1. ELEVATOR
 OPERATION SHALL BE AUTOMATIC.
  
 3B)HANDRAIL/ GUARDRAIL COMPLIED SHEET 327 A DETAIL
 SHEET.
  
 4) BOTH SHEETS A 2ND FLOOR REFLECTED CEILING PLAN & A
 PROPOSED ROOF PLAN AND SHEET 329 ROOF DETAILS, DETAIL 2
 SHOW ROOF TOP ACCESS WITH A ROOF HATCH. PLEASE REVIEW
 ROOF TOP HATCH SIZE REQUIREMENTS UNDER 2017 FBC-B
 1011.12.2 ROOF ACCESS.
 EXCEPTION: IN BUILDINGS WITHOUT AN OCCUPIED ROOF,
 ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF
 HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE FEET IN AREA
 AND HAVING A MINIMUM DIMENSION OF 2 FEET.
  
 5) THE 2ND FLOOR PLAN DOES NOT SHOW ANY OF THE PROPOSED
 CHASES FOR THE FUTURE KITCHEN EQUIPMENT ON THE
 ARCHITECTURAL SHEET THAT ARE SHOWN ON THE M1.02 2ND
 FLOOR PLAN. PLEASE ALSO NOTE THE S2.1 ALSO IS MISSING
 THE BLOCK OUTS IN THE NEW 2ND FLOOR SLAB. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED ON THE A & S SHEETS.
  
 6) STRUCTURAL SHEETS INDICATE THE STAIRS TO THE 2ND
 FLOOR ARE TO BE DESIGNED BY A SPECIALTY ENGINEER.
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE ARCHITECTURAL SHEET A STAIR PLAN DOES NOT
 PROVIDE A VERTICAL SECTION OF THE STAIRS. IT IS NOT
 CLEAR IF THE UNDER THE STAIR WAY WHAT OCCURS, NO
 STORAGE. FBC-B 1011.7.3. ENCLOSURES UNDER INTERIOR
 STAIRWAYS. ALSO LOOK AT THE ACCESS. CODE 307.4 VERTICAL
 CLEARANCES AND FIGURE 307.4.
  
 8) THE SUBMITTED PLAN A DETAILS SHOW A TRASH ENCLOSURE
 AND PRECAST CONCRETE WALL SYSTEM. THESE ITEMS WILL
 REQUIRE A SEPARATE PERMIT, NOT PART OF THIS REVIEW VOID
 DETAILS. DETAILS INDICATE SCREEN WALL DESIGN INDICATE
 THE DEPTH AND DIAMETER OF FOUNDATION TO BE DETERMINED.
  
 9) SHEET 328 A ROOF DETAILS, DETAIL 3 WILL NEED TO
 COMPLY WITH THE HEIGHT REQUIREMENTS FOR ROOF TOP
 EQUIPMENT SEE THE 2017 FBC-B TABLE 15.10 CLEARANCE
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 10) SHEET 317A PROPOSED ROOF PLAN NOTE # 12 DOES NOT
 MATCH THE DETAIL SHEET 329A ROOF DETAILS. SHEET 317A
 NOTE # 12 INDICATES A PROPOSED 4 FOOT HIGH LOUVERED
 ROOF TOP EQUIPMENT SCREEN: WILLARD SHUTTER CO.
 ECONOSPAN 45 DEGREES PITCHED LOUVER. G. C. TO PROVIDE
 SHOP DRAWINGS. DISCREPANCY IN NOTE 12 VERSUS THE
 DETAILS ON SHEET A317. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN PLANS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) SHEET 401SS1.1. THE WALL PRESSURE CHART IN VASD AND
 KD= 0.85, MEAN ROOF HEIGHT OF 21 FEET(USING 20 FOOT
 MEAN ROOF HEIGHT FROM CHARTS), NO 3 FOOT PARAPET, THE
 OPENING PRESSURES ARE BETWEEN 2.8 TO 3 PSF LOWER THAN
 THE ASCE CHARTS AND ENGINEER FRANK BONNARD?S CHARTS.
 YOUR RANGE OF OPENING SIZES ALSO DOES NOT LINE UP TO
 THE ASCE CHARTS EITHER. YOU START AT 0-19 SQ. FT. OF
 TRIBUTARY OR EFFECTIVE WIND AREA DEPENDING ON IF YOU
 ARE USING THE ASCE OR CHART IN 1609 OF THE FBC-B CODE
 BOOK WHERE THESE CHARTS ARE STARTING AT 10 FEET. PLEASE
 PROVIDE WHY YOUR PRESSURES ARE LOWER? ROOF PRESSURES ON
 SHEET 400 S.S1 PRESSURES ARE GOOD.
  
 12) SHEET 400S. S1 UNDER THE HEADING OF SHALLOW
 FOUNDATION MENTIONS A SOILS REPORT BY GEOTECHNICAL
 MATERIAL TESTING INSPECTION SERVICES DATED 01/18/2018,
 PLEASE SUBMIT THE REPORT FOR ITS FINDINGS.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 PLEASE SUBMIT EITHER IF IN PAPER AN ORIGINAL SIGNED AND
 SEALED REPORT. IF ELECTRONICALLY THE REPORT WILL NEED
 TO BE SIGNED AND SEALED ELECTRONICALLY.
  
 13) THIS PROJECT HAS BOLTED STEEL CONNECTIONS AS WELL
 AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS REQUIRED
 TO PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 14) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 15A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 15C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 17A) ROOFING PRODUCT APPROVALS: FOR ALL ROOFING
 PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND
 THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW
 THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING
 IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET
 AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 17B) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, VENTING, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 18) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  