2019-06-25 13:56:10 | MECHANICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THERE IS NO RECORD OF THE 10X12 A/C VENT BEING |
| PERMITTED. SHOW AS PROPOSED AND INCLUDE IN ENERGY |
| CALCULATIONS FOR SYSTEM SIZING. |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| |
| 2. PROVIDE MECHANICAL RISER DIAGRAHM. INCLUDE THE |
| PROPOSED 10X12 VENT AND REQUIRED RETURN AIR VENT. |
| FBC E R403.7.1EQUIPMENT SIZING. |
| HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| OTHER APPROVED HEATING AND COOLING CALCULATION |
| METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| CONDITIONS DESCRIBED IN SECTION R302.1 |
| |
| 3. NOTE ON PLAN STATES SYSTEM IS A 4 TON UNIT. PROVIDE |
| MAKE AND MODEL NUMBER OF AHU & CU. |
| M1202.1ADDITIONS, ALTERATIONS OR REPAIRS. |
| ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO A |
| MECHANICAL SYSTEM SHALL CONFORM TO THE REQUIREMENTS FOR |
| A NEW MECHANICAL SYSTEM WITHOUT REQUIRING THE EXISTING |
| MECHANICAL SYSTEM TO COMPLY WITH ALL OF THE |
| REQUIREMENTS OF THIS CODE. ADDITIONS, ALTERATIONS OR |
| REPAIRS SHALL NOT CAUSE AN EXISTING MECHANICAL SYSTEM |
| TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. MINOR |
| ADDITIONS, ALTERATIONS OR REPAIRS TO EXISTING |
| MECHANICAL SYSTEMS SHALL MEET THE PROVISIONS FOR NEW |
| CONSTRUCTION, UNLESS SUCH WORK IS DONE IN THE SAME |
| MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM, |
| IS NOT HAZARDOUS, AND IS APPROVED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |