2019-06-25 13:56:10MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE IS NO RECORD OF THE 10X12 A/C VENT BEING
 PERMITTED. SHOW AS PROPOSED AND INCLUDE IN ENERGY
 CALCULATIONS FOR SYSTEM SIZING.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 2. PROVIDE MECHANICAL RISER DIAGRAHM. INCLUDE THE
 PROPOSED 10X12 VENT AND REQUIRED RETURN AIR VENT.
 FBC E R403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1
  
 3. NOTE ON PLAN STATES SYSTEM IS A 4 TON UNIT. PROVIDE
 MAKE AND MODEL NUMBER OF AHU & CU.
 M1202.1ADDITIONS, ALTERATIONS OR REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO A
 MECHANICAL SYSTEM SHALL CONFORM TO THE REQUIREMENTS FOR
 A NEW MECHANICAL SYSTEM WITHOUT REQUIRING THE EXISTING
 MECHANICAL SYSTEM TO COMPLY WITH ALL OF THE
 REQUIREMENTS OF THIS CODE. ADDITIONS, ALTERATIONS OR
 REPAIRS SHALL NOT CAUSE AN EXISTING MECHANICAL SYSTEM
 TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. MINOR
 ADDITIONS, ALTERATIONS OR REPAIRS TO EXISTING
 MECHANICAL SYSTEMS SHALL MEET THE PROVISIONS FOR NEW
 CONSTRUCTION, UNLESS SUCH WORK IS DONE IN THE SAME
 MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM,
 IS NOT HAZARDOUS, AND IS APPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  