2019-06-25 14:20:41ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PANEL SCHEDULE. INCLUDE ANY NEW CIRCUTS.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902.
  
 2. PANEL SHALL BE LABELED.
 E3401.4 ADDITIONS AND ALTERATIONS.
 ANY ADDITION OR ALTERATION TO AN EXISTING ELECTRICAL
 SYSTEM SHALL BE MADE IN CONFORMITY TO THE PROVISIONS OF
 CHAPTERS 34 THROUGH 43.
  
 3. OUTLET SPACING SHALL COMPLY WITH E3901.2.1.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1.
  
 4. PLAN INDICATES MAIN BREAKER PANEL IS 125 AMPS.
 PUBLIC RECORDS INDICATE EXISTING PANEL TO BE 150 AMPS.
 PLEASE CLARIFY.
  
 5. LOAD CALCULATION PAGE REQUIRES ORIGINAL SIGNATURE OF
 CONTRACTOR.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 6. SMOKE ALARMS SHALL COMPLY WITH R314.
  
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
  
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 EXCEPTIONS:
 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS,
 SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE
 ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE
 ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR
 MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF
 THIS SECTION.
  
 R314.4 INTERCONNECTION.
 WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN
 ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL
 BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION
 OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE
 INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF
 SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED
 WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON
 ACTIVATION OF ONE ALARM.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  