2019-06-07 10:49:16 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19051313 |
| REVIEWED: JUNE 7, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| |
| 1) 105.2 FBC[B] WORK EXEMPT FROM PERMIT. EXEMPTIONS |
| FROM PERMIT REQUIREMENTS OF THIS CODE SHALL NOT BE |
| DEEMED TO GRANT AUTHORIZATION FOR ANY WORK TO BE DONE |
| IN ANY MANNER IN VIOLATION OF THE PROVISIONS OF THIS |
| CODE OR ANY OTHER LAWS OR ORDINANCES OF THIS |
| JURISDICTION. PERMITS SHALL NOT BE REQUIRED FOR THE |
| FOLLOWING: |
| |
| REPLACEMENT OF CABINETS AND COUNTERTOPS WITHOUT |
| RECONFIGURATION, PAINTING, PAPERING, TILING, CARPETING, |
| AND SIMILAR FINISH WORK, WITH NO ELECTRICAL OR PLUMBING |
| WORK. THIS EXCEPTION DOES NOT INCLUDE HARD FLOORING |
| IMMEDIATELY ABOVE ADJACENT DWELLING UNITS, OR OTHER |
| WORK FOR WHICH THERE ARE SPECIFIC REQUIREMENTS IN |
| FLORIDA BUILDING CODE THAT AFFECT THE PROPOSED WORK. |
| - IF NO RECONFIGURATION THEN NO PERMIT NEEDED FOR |
| COUNTERTOPS AND CABINETS. HOWEVER, THE FLOORING DOES |
| NEED PERMIT FOR SOUND TRANSMISSION SUBMITTAL. |
| |
| 2) 1207.2 FBC[B] FLOORING SUBMITTAL. |
| - FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE |
| OF FLOORING FOR EACH AREA. |
| |
| 3) 1207.2 FBC[B] FLOORING SUBMITTAL. |
| - TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF |
| CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT |
| BELOW. |
| |
| 4) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT |
| FLOORING AND UNDERLAYMENT ARE PROPOSED? IF THE |
| UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR WHICH WE |
| HAVE TEST REPORTS ON FILE, THE FOLLOWING REPORTS WILL |
| BE REQUIRED: |
| 4A) 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS |
| AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS |
| AND SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E90. |
| 4B) 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| ACCORDANCE WITH ASTM E492. |
| 4C) 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| - THE PERMIT SAYS LAY TILE OVER. IS THE INTENET TO |
| LEAVE TO EXISTING FLOO?. PROVIDE DATA FOR WHAT WAS |
| PREVIOUSLY INSTALLED TO SHOW HOW IT WILL MEET CURRENT |
| SOUND TRANSMISSION REQUIREMENTS. |
| |
| NOTES: |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |
| |
| |