Plan Review Notes
Plan Review Notes For Permit 19051313
Permit Number 19051313
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-07 10:49:16BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19051313
 REVIEWED: JUNE 7, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
  
 1) 105.2 FBC[B] WORK EXEMPT FROM PERMIT. EXEMPTIONS
 FROM PERMIT REQUIREMENTS OF THIS CODE SHALL NOT BE
 DEEMED TO GRANT AUTHORIZATION FOR ANY WORK TO BE DONE
 IN ANY MANNER IN VIOLATION OF THE PROVISIONS OF THIS
 CODE OR ANY OTHER LAWS OR ORDINANCES OF THIS
 JURISDICTION. PERMITS SHALL NOT BE REQUIRED FOR THE
 FOLLOWING:
  
 REPLACEMENT OF CABINETS AND COUNTERTOPS WITHOUT
 RECONFIGURATION, PAINTING, PAPERING, TILING, CARPETING,
 AND SIMILAR FINISH WORK, WITH NO ELECTRICAL OR PLUMBING
 WORK. THIS EXCEPTION DOES NOT INCLUDE HARD FLOORING
 IMMEDIATELY ABOVE ADJACENT DWELLING UNITS, OR OTHER
 WORK FOR WHICH THERE ARE SPECIFIC REQUIREMENTS IN
 FLORIDA BUILDING CODE THAT AFFECT THE PROPOSED WORK.
 - IF NO RECONFIGURATION THEN NO PERMIT NEEDED FOR
 COUNTERTOPS AND CABINETS. HOWEVER, THE FLOORING DOES
 NEED PERMIT FOR SOUND TRANSMISSION SUBMITTAL.
  
 2) 1207.2 FBC[B] FLOORING SUBMITTAL.
 - FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE
 OF FLOORING FOR EACH AREA.
  
 3) 1207.2 FBC[B] FLOORING SUBMITTAL.
 - TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 4) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT
 FLOORING AND UNDERLAYMENT ARE PROPOSED? IF THE
 UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR WHICH WE
 HAVE TEST REPORTS ON FILE, THE FOLLOWING REPORTS WILL
 BE REQUIRED:
 4A) 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 AND SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 4B) 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 4C) 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 - THE PERMIT SAYS LAY TILE OVER. IS THE INTENET TO
 LEAVE TO EXISTING FLOO?. PROVIDE DATA FOR WHAT WAS
 PREVIOUSLY INSTALLED TO SHOW HOW IT WILL MEET CURRENT
 SOUND TRANSMISSION REQUIREMENTS.
  
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  
  
  