2019-08-15 10:27:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 ORIGINAL COMMENTS
 1) COMPLIED
 2) COMPLIED
 3) COMPLIED
 4) SHT. S1 TOILET DETAIL SHOWS 15? TO TOP OF TOILET.
 THE TOILET SHALL BE BETWEEN 17?-19?-ACC 604.4. COMMENT:
 SEE RED LINED COMMENT ON S1; FIXTURE ELEVATION AND
 COMPLY.
 5) SHT.S1 TOILET DISPENSER SHALL BE SHOWN AS 7?-9? FROM
 THE FRONT LIP OF THE BOWL. FBC-ACC 604.7. COMMENT: SEE
 RED LINED COMMENT ON S1; FIXTURE ELEVATION AND COMPLY.
 6) COMPLIED
 7) SHT. S1 TOILET GRAB BAR DETAIL PROVIDE SHOWS GRAB
 BAR MOUNT TO THE CENTER OF BAR. THE 33"-36" SHALL BE TO
 THE TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4.
 COMMENT: SEE RED LINED COMMENT ON S1; FIXTURE ELEVATION
 AND COMPLY.
 8) WILL THE LAB-SINK ALSO BE USED AS A BREAK ROOM SINK?
 IF SO, PLEASE PROVIDE CABINET TOP AND CLEAR FLOOR SPACE
 DETAIL. FBC 107.2.1. COMMENT: SHOW DIMENSIONED CLEAR
 FLOOR SPACE FOR THE SINK TO COMPLY WITH FBC ACC 305.
  
 NEW COMMENTS
 1) SHT. E1; SANITARY RISER: THE NEW H/C SINK MAY BE
 VENTED WITH AN AIR ADMITTANCE VALVE AS NOTED, HOWEVER
 THE NEW UNDERGROUND PIPING NEEDS TO BE AN EXTENSION OF
 THE EXISTING HORIZONTAL WET VENT SERVICING THE WATER
 CLOSET AND SHALL CONNECT TO IT IN A MANNER THAT THERE
 IS NO HORIZONTAL DRY PORTION OF THE ORIGINAL VENT AT
 THE ORIGINAL BATHROOM SINK. TO BE CLEAR, DO NOT CONNECT
 DOWNSTREAM OF THE ORIGINAL VERTICAL VENT. PER WPB FBC
 107.2.1, SHOW THIS ON THE RISER DIAGRAM.
 2) IS THE RELOCATED BREAKROOM SINK GOING TO CONNECT TO
 THE ORIGINAL VERTICAL WASTE/VENT? IF SO, PER WPB FBC
 107.2.12, PROVIDE A PLUMBING NOTE STATING SUCH AND
 PROVIDE FOR AN AIR ADMITTANCE VALVE AT THE FIXTURE IF
 THE DRAIN LENGTH EXCEEDS THE REQUIREMENTS OF FBC PL
 909.1 AND TABLE 909.1. OTHERWISE PROVIDE A SANITARY
 RISER DIAGRAM SHOWING HOW THE FIXTURE WILL BE DRAINED
 AND VENTED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH