2019-06-11 12:28:33 | PLUMBING 1ST REVIEW**DENIED** |
| |
| 1) SHT. CVR: OCCUPANT LOAD SHALL BE ROUNDED UP TO 15. |
| PROVIDE OVERALL DIMENSION OF THE COMBINED SPACE. |
| OCCUPANCY IS LISTED AS STORAGE AND BUSINESS, BUT I AM |
| NOT ABLE TO LOCATE THE STORAGE AREA. PLEASE CLARIFY. |
| FBC 107.3.5 |
| |
| 2) SHT. CRV UNDER ACCESSIBILITY NOTES LIST TO COMPLY |
| WITH THE 2014 FLORIDA ACCESSIBILITY. CURRENT CODE IS |
| THE 2017 FLORIDA ACCESSIBILITY CODE. FBC 107.2.1 |
| |
| 3) SHT. S1 LIST SIDE GRAB BAR AS 11? FROM BACK WALL. |
| YOUR SHOW A 42? BAR WHICH MUST BE MOUNTED @ 12? FROM |
| REAR WALL TO GET THE REQUIRED 54? OVERALL. FBC-ACC |
| 604.5.1 |
| |
| 4) SHT. S1 TOILET DETAIL SHOWS 15? TO TOP OF TOILET. |
| THE TOILET SHALL BE BETWEEN 17?-19? TO THE SEAT. |
| FBC-ACC 604.4 |
| |
| 5) SHT.S1 TOILET DISPENSER SHALL BE SHOWN AS 7?-9? FROM |
| THE FRONT LIP OF THE BOWL. FBC-ACC 604.7 |
| |
| 6) SHT.CVR CALLS OUT NO PLUMBING WORK TO BE DONE. |
| PLEASE CLARIFY. FBC 107.2.1 |
| |
| 7) SHT. S1 TOILET GRAB BAR DETAIL PROVIDE SHOWS GRAB |
| BAR MOUNT TO THE CENTER OF BAR. THE 33?-36? SHALL BE TO |
| THE TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4 |
| |
| 8) WILL THE LAB-SINK ALSO BE USED AS A BREAK ROOM SINK? |
| IF SO PLEASE PROVIDE CABINET TOP AND CLEAR FLOOR SPACE |
| DETAIL. FBC 107.2.1 |
| |
| |
| |