2019-07-08 10:38:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER SQ.
 FT. IS REQUIRED FOR THE LAB PER TABLE 403.3.1.1 FBC M.
 PLEASE PROVIDE A CALCULATION, SHOW DETAILS AND
 SPECIFICATIONS FOR THE SYSTEM, AND THE SYSTEM'S
 SEQUENCE OF OPERATION.
  
 2) PROVIDE ON THE PLAN A NARRATIVE THAT DESCRIBES THE
 PROCESSES THAT OCCUR IN THE LAB, WHAT EQUIPMENT IS
 USED, AND A LIST MATERIALS TO BE USED AND STORED IN THE
 LAB- SECTION 107.2.1 WPB, AND SECTIONS 414.2.1 &
 414.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  