2019-07-11 08:47:22 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19051312 |
| REVIEWED: JULY 10, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 107.5.3 FBC[AMENDED] CODE EDITION. |
| - COVER SHEET SAYS ACCESSIBILITY 2014. THIS SHOULD BE |
| 2017 FLORIDA BUILDING CODE ACCESSIBILITY 6TH EDITION. |
| |
| 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| WORK BEING PERFORMED. |
| A) LEVEL 1 ALTERARTION |
| B) LEVEL 2 ALTERARTION |
| C) LEVEL 3 ALTERARTION |
| - LEVEL OF ALTERATION SHOULD BE LEVEL 2 SINCE WALLS ARE |
| BEING REMOVED AND REPLACED. |
| |
| 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING |
| MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS |
| FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL |
| BE DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| - OCCUPANT LOAD SHOULD BE 15 PERSONS. SINCE SQ. FOOTAGE |
| EXCEEDS 1400 IT ROUNDS UP TO 1500. |
| |
| 4) 404.2.4 FBC[A] MANEUVERING CLEARANCES. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS |
| - SHOW CLEAR SPACE AT EXAM ROOM 3 FROM ROOM INTERIOR. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |