2019-07-01 12:05:20 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19051286 |
| 7/1/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) EXHAUST VENTILATION IS REQUIRED FOR THE UPS SYSTEM, |
| HOWEVER DETERMINING HOW THE SYSTEM WILL BE VENTILATED |
| IS DEPENDENT ON SUBMITTAL OF MSDS SHEETS FOR THE |
| BATTERIES, AND CLARIFICATION OF HOW THE BATTERIES ARE |
| BEING STORED, AND BATTERY QUANTITIES- SEE FBC M CODE |
| SECTIONS BELOW. |
| |
| 502.4 STATIONARY STORAGE BATTERY SYSTEMS. |
| STATIONARY STORAGE BATTERY SYSTEMS, AS REGULATED BY THE |
| FLORIDA FIRE PREVENTION CODE, SHALL BE PROVIDED WITH |
| VENTILATION IN ACCORDANCE WITH THIS CHAPTER AND SECTION |
| 502.4.1 OR 502.4.2. |
| EXCEPTION: LITHIUM-ION AND LITHIUM METAL POLYMER |
| BATTERIES SHALL NOT REQUIRE ADDITIONAL VENTILATION |
| BEYOND THAT WHICH WOULD NORMALLY BE REQUIRED FOR HUMAN |
| OCCUPANCY OF THE SPACE. |
| |
| 502.4.1 HYDROGEN LIMIT IN ROOMS. |
| FOR FLOODED LEAD ACID, FLOODED NICKEL CADMIUM AND VRLA |
| BATTERIES, THE VENTILATION SYSTEM SHALL BE DESIGNED TO |
| LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 |
| PERCENT OF THE TOTAL VOLUME OF THE ROOM. |
| |
| 502.4.2 VENTILATION RATE IN ROOMS. |
| CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF |
| NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER SQUARE FOOT |
| (CFM/FT2) OF FLOOR AREA OF THE ROOM. |
| |
| 502.4.3 SUPERVISION. |
| MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION |
| 502.4 SHALL BE SUPERVISED BY AN APPROVED CENTRAL, |
| PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE |
| AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED |
| ON-SITE LOCATION. |
| |
| 502.5 VALVE-REGULATED LEAD-ACID BATTERIES IN CABINETS. |
| VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES INSTALLED IN |
| CABINETS, AS REGULATED BY THE FLORIDA FIRE PREVENTION |
| CODE, SHALL BE PROVIDED WITH VENTILATION IN ACCORDANCE |
| WITH SECTION 502.5.1 OR 502.5.2. |
| |
| 502.5.1 HYDROGEN LIMIT IN CABINETS. |
| THE CABINET VENTILATION SYSTEM SHALL BE DESIGNED TO |
| LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 |
| PERCENT OF THE TOTAL VOLUME OF THE CABINET DURING THE |
| WORST-CASE EVENT OF SIMULTANEOUS BOOST CHARGING OF ALL |
| BATTERIES IN THE CABINET. |
| |
| 502.5.2 VENTILATION RATE IN CABINETS. |
| CONTINUOUS CABINET VENTILATION SHALL BE PROVIDED AT A |
| RATE OF NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER |
| SQUARE FOOT (CFM/FT2) OF THE FLOOR AREA COVERED BY THE |
| CABINET. THE ROOM IN WHICH THE CABINET IS INSTALLED |
| SHALL BE VENTILATED AS REQUIRED BY SECTION 502.4.1 OR |
| 502.4.2. |
| |
| 502.5.3 SUPERVISION. |
| MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION |
| 502.5 SHALL BE SUPERVISED BY AN APPROVED CENTRAL, |
| PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE |
| AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED |
| ON-SITE LOCATION. |
| |
| 2) PROVIDE THE FOLLOWING INFORMATION FOR THE UPS |
| SYSTEMS AS OUTLINED IN SECTION 414.1.3 FBC B. PLEASE |
| NOTE THAT THE WALLS ENCLOSING THE UPS ROOM MAY HAVE TO |
| BE FIRE-RATED. |
| |
| 414.1.3 INFORMATION REQUIRED. |
| A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF |
| HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED |
| SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO |
| SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION |
| CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE |
| METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT |
| NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS |
| AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE |
| REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION |
| AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, |
| FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL |
| AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY. |
| |
| 3) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES INVOLVED IN THE PROPSED ALTERATION PER |
| TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE |
| THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF |
| OUTDOOR AIR. |
| |
| 4) THE NOTES ON THE PLANS INDICATE THE EQUIPMENT- |
| CHILLERS, IRC'S, CDU'S, AND UPS BATTERY SYSTEMS ARE |
| OWNER SUPPLIED, HOWEVER TOTAL VALUE FOR PERMITTING IS |
| BASED ON ALL LABOR, MATERIAL, EQUIPMENT, DESIGN FEES, |
| PROFIT SAND OVERHEAD. PLEASE REFER TO SECTION 109.3 WPB |
| AND PROVIDE BONA-FIDE CONTRACTS, INVOICES, AND |
| ESTIMATES TO VERIFY THE TOTAL COST OF THE PROJECT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |