2019-07-03 16:15:40FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE WORK SHOWN IS TOO LOW.
  
 1A) PLEASE INDICATE ALL EQUIPMENT AND VALUE THAT IS
 SUPPLIED BY THE OWNER
 UPS, BATTERY, AC, BUSS DUCT ECT. ECT.
 VALUES SENT IN EMAIL NOT REALISTIC FOR EQUIPMENT SHOWN
  
 1B) PLEASE INDICATE VALUE FOR EACH PCS. OF EQUIPMENT
 SUPPLIED BY OWNER AND CUT SHEETS TO GO WITH EQUIPMENT
 SO WE CAN UNDERSTAND WHAT IS WHAT.
  
 2) NEED TO SUBMIT CUT SHEETS AND INDICATE WHICH MODEL
 YOU ARE USING. BUSS DUCT, BATTERIES, AC, UPS, SWITCH
 GEAR, CABLES DLO
  
 3) RISER DIAGRAM PLEASE INDICATE WHICH IS EXISTING WORK
 AND WHICH IS NEW WORK.
  
 4) HOW MANY MAINS ARE IN THE BUILDING 3000A LOOKS TO BE
 NEW. WHAT IS THE EXISTING SIZE AND HOW AMNY MAINS ARE
 THERE IN BUILDING????????
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE
 A RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED
 PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE
 OR VOID THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
  
  
  
  
  