Plan Review Notes For Permit 19051286 |
Permit Number |
19051286 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-07-03 17:01:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC B 1609, SEE PREVIOUS LIST, I WAS UNABLE TO | | LOCATE WIND DESIGN CRITERIA (WIND SPEED, EXPOSURE, | | DESIGN PRESSURES). | | | | 2. OK | | | | 3. THE DOOR PRODUCT APPROVAL WAS PROVIDED, BUT I WAS | | UNABLE TO LOCATE AN OPTION FOR A PANIC BAR/FIRE EXIT | | HARDWARE IN THE PRODUCT APPROVAL. EITHER CIRCLE ON THE | | PRODUCT APPROVAL OR PROVIDE A NEW ONE WHICH INCLUDES | | THIS OPTION. | | | | FBC 107, PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER | | OF RECORD. | | | | |
|