Plan Review Notes For Permit 19051286 |
Permit Number |
19051286 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-05 17:26:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC B 1609, SHEETS M503, PROVIDE A STRUCTURAL DETAIL | | FOR THE NEW DOOR OPENING. IF SHEET M503 IS ELIMINATED | | AND THE STRUCTURAL PAGE IS REVISED TO INCLUDE THE DOOR | | DETAIL, PLEASE SPECIFY PANIC BAR AS SHOWN ON M503. | | | | THE DETAIL PROVIDED LACKS WIND DESIGN CRITERIA, LINTEL | | SPEC (ONLY STATES "PAINTED STEEL LINTEL"), LINTEL | | INSTALLATION SPECIFICS, DOES NOT SHOW FILLED CELLS ON | | EITHER SIDE OF THE NEW DOOR, ETC. | | | | 2. FBC 107, REVISE PLAN TO SHOW LOCATION OF NEW DOOR. | | | | 3. FBC B 1609, PROVIDE DOOR PRODUCT APPROVAL REVIEWED | | BY DESIGNER OF RECORD. | | |
|