2019-06-05 17:26:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, SHEETS M503, PROVIDE A STRUCTURAL DETAIL
 FOR THE NEW DOOR OPENING. IF SHEET M503 IS ELIMINATED
 AND THE STRUCTURAL PAGE IS REVISED TO INCLUDE THE DOOR
 DETAIL, PLEASE SPECIFY PANIC BAR AS SHOWN ON M503.
  
 THE DETAIL PROVIDED LACKS WIND DESIGN CRITERIA, LINTEL
 SPEC (ONLY STATES "PAINTED STEEL LINTEL"), LINTEL
 INSTALLATION SPECIFICS, DOES NOT SHOW FILLED CELLS ON
 EITHER SIDE OF THE NEW DOOR, ETC.
  
 2. FBC 107, REVISE PLAN TO SHOW LOCATION OF NEW DOOR.
  
 3. FBC B 1609, PROVIDE DOOR PRODUCT APPROVAL REVIEWED
 BY DESIGNER OF RECORD.
  