Plan Review Notes
Plan Review Notes For Permit 19051283
Permit Number 19051283
Review Stop G
Sequence Number 1
Notes
Date Text
2019-05-29 07:08:30GAS 1ST REVIEW**DENIED**
  
 1) VALUATION MUST INCLUDE THE GAS COOK TOP. MASTER #
 19010757 CALLS OUT THE COOK TOP AS ELC. REVISE VALUE OF
 JOB TO INCLUE THE GAS COOK TOP. WPB AMEND 109.3
  
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBCR
 G2407.9.3
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) PERSON DESIGNING PLAN SHALL SIGN AND DATE TAKING
 RESPONSIBLENESS. F.S 471,481, 489
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  