Plan Review Notes For Permit 19051283 |
Permit Number |
19051283 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-29 07:08:30 | GAS 1ST REVIEW**DENIED** | | | | 1) VALUATION MUST INCLUDE THE GAS COOK TOP. MASTER # | | 19010757 CALLS OUT THE COOK TOP AS ELC. REVISE VALUE OF | | JOB TO INCLUE THE GAS COOK TOP. WPB AMEND 109.3 | | | | 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS | | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBCR | | G2407.9.3 | | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | 4) PERSON DESIGNING PLAN SHALL SIGN AND DATE TAKING | | RESPONSIBLENESS. F.S 471,481, 489 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | |
|