2019-06-04 07:51:29GAS 1ST REVIEW**DENIED**
  
 1) YOUR SURVEY CALLS OUT A #1 POUND SYSTEM BUT DO NOT
 SHOWN OR HAVENT PROVIDE SIZING CHARTS FOR THAT PRESSURE
 SYSTEM. PLEASE CLARIFY. FBC 107.2.1
  
 2) GENERATOR IS 312,000 BTU'S PER THE INSTALLATION
 MANUAL AND NOT 240,00 BTU'S AS CALLED OUT ON YOUR PLAN.
 BASED ON THE SIZING CHART PROVIDED 402.4 (1) MAX
 PERMITTED BTU'S WOULD BE 273,000 BTU'S. FBC 107.2.1
  
 3) PROVIDE PIPE SIZE WHERE YOU PLAN ON CONNECTING INTO
 THE EXISTING GAS SYSTEM. FBC 107.3.5
  
 4) YOU PROVIDED PRESSURE REGULATOR SPEC BUT DO NOT SHOW
 SYSTEM AS 2 PSI OR ADDING TO THE EXISTING EQUIPMENT.
 PLEASE CLARIFY AND CALL OUT THE PSI OF THE EXISTING
 SYSTEM. FBC 107.3.5
  