2019-06-06 15:20:57 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| BUILDING PLAN REVIEW DENIED: |
| |
| 1. FBC B 107.2.1 PROVIDE MORE INFORMATION: |
| A. OCCUPANT LOAD FOR SECTION "B". |
| B. DETAILS INCLUDING DIMENSIONS FOR INTERIOR DOOR ALONG |
| THE COMMON PATH OF TRAVEL IN SECTION "B". |
| 2. FBC B 1010.1.2.1 DIRECTION OF DOOR SWING FOR THE |
| INTERIOR DOOR ALONG THE COMMON PATH OF TRAVEL IN |
| SECTION "B". |
| 3. FBC B 107.2.1 PROVIDEWALL SPECIFIC SECTIONDETAILFOR |
| WALL "C". |
| |
| PLEASE DISREGARD BUILDING COMMENTS FROM 6/5/19. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| RESULT IN NEW PLAN REVIEW COMMENTS. |
2019-06-05 10:40:24 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19050860 |
| ADD: 901 45TH ST. ST. MARY?S MEDICAL CENTER |
| CONT: WESTBROOKE CORPORATION |
| TEL: 561-395-4126 |
| E-MAIL: |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 06/ 2019 |
| ACTION: DENIED |
| |
| 1) SHEET AD3.2 INDICATES WITH NOTES 1 & 2 DEMOLITION |
| WORK OF AN EXTERIOR WALL (NOTE # 1 REMOVE AN EXISTING |
| PORTION OF WALL, PREPARE FOR LOUVER INSTALLATION. NOTE |
| # 2 INDICATES THE REMOVAL OF FLOORING. |
| SHEET A3.2 NOTE # 3 INDICATES A NEW HVAC PENETRATION |
| THROUGH THE FLOOR SYSTEM. THE ARCHITECTURAL SHEETS GIVE |
| NO FURTHER INFORMATION ON THE NEW OPENING IN THE WALL |
| SYSTEM HOW TO PREPARE THE WALL OPENING FOR THE NEW |
| LOUVER. NOR DOES THE ARCHITECTURAL SHEETS PROVIDE |
| INFORMATION AS TO THE STEPS INVOLVED FOR THE NEW FLOOR |
| PENETRATION, TYPE OF FLOOR SYSTEM, NOR IF ANY |
| ADDITIONAL BRACING WILL BE REQUIRED THE NEW OPENING. |
| |
| THE COVERSHEET A0.0 DOES HAVE A INDEX OF DRAWINGS AN IT |
| APPEARS THAT THE S-100 STRUCTURAL SHEET WAS LEFT OUT OF |
| BOTH SETS OF PLANS. THE UNKNOWN SHEET WOULD HAVE TO |
| ANSWER BOTH THE QUESTIONS STATED ABOVE PLUS PROVIDE THE |
| WIND DESIGN CRITERIA FOR 180 VULT, MEAN ROOF HEIGHT AND |
| THE ASSOCIATED PRESSURES FOR THE NEW WALL LOUVER. |
| ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2. |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |