Plan Review Notes
Plan Review Notes For Permit 19051226
Permit Number 19051226
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-06 15:20:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW DENIED:
  
 1. FBC B 107.2.1 PROVIDE MORE INFORMATION:
 A. OCCUPANT LOAD FOR SECTION "B".
 B. DETAILS INCLUDING DIMENSIONS FOR INTERIOR DOOR ALONG
 THE COMMON PATH OF TRAVEL IN SECTION "B".
 2. FBC B 1010.1.2.1 DIRECTION OF DOOR SWING FOR THE
 INTERIOR DOOR ALONG THE COMMON PATH OF TRAVEL IN
 SECTION "B".
 3. FBC B 107.2.1 PROVIDEWALL SPECIFIC SECTIONDETAILFOR
 WALL "C".
  
 PLEASE DISREGARD BUILDING COMMENTS FROM 6/5/19.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
2019-06-05 10:40:242017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050860
 ADD: 901 45TH ST. ST. MARY?S MEDICAL CENTER
 CONT: WESTBROOKE CORPORATION
 TEL: 561-395-4126
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 06/ 2019
 ACTION: DENIED
  
 1) SHEET AD3.2 INDICATES WITH NOTES 1 & 2 DEMOLITION
 WORK OF AN EXTERIOR WALL (NOTE # 1 REMOVE AN EXISTING
 PORTION OF WALL, PREPARE FOR LOUVER INSTALLATION. NOTE
 # 2 INDICATES THE REMOVAL OF FLOORING.
 SHEET A3.2 NOTE # 3 INDICATES A NEW HVAC PENETRATION
 THROUGH THE FLOOR SYSTEM. THE ARCHITECTURAL SHEETS GIVE
 NO FURTHER INFORMATION ON THE NEW OPENING IN THE WALL
 SYSTEM HOW TO PREPARE THE WALL OPENING FOR THE NEW
 LOUVER. NOR DOES THE ARCHITECTURAL SHEETS PROVIDE
 INFORMATION AS TO THE STEPS INVOLVED FOR THE NEW FLOOR
 PENETRATION, TYPE OF FLOOR SYSTEM, NOR IF ANY
 ADDITIONAL BRACING WILL BE REQUIRED THE NEW OPENING.
  
 THE COVERSHEET A0.0 DOES HAVE A INDEX OF DRAWINGS AN IT
 APPEARS THAT THE S-100 STRUCTURAL SHEET WAS LEFT OUT OF
 BOTH SETS OF PLANS. THE UNKNOWN SHEET WOULD HAVE TO
 ANSWER BOTH THE QUESTIONS STATED ABOVE PLUS PROVIDE THE
 WIND DESIGN CRITERIA FOR 180 VULT, MEAN ROOF HEIGHT AND
 THE ASSOCIATED PRESSURES FOR THE NEW WALL LOUVER.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved