2019-05-28 13:43:551) THE RECORD GAS DRAWINGS ON FILE IN THE CITY SHOW THE
 FOLLOWING BTU VALUES FOR THE LISTED APPLIANCES:
 POOL HEATER - 400,000 BTU'S
 DRYER - 40,000 BTU'S
 FIRELOGS - 44,000
 GENERATOR - 560,000 BTU'S
 RANGE - 300,000 BTU'S
 WATER HEATER - 75,000
 TOTAL BTU LOAD - 1,419,000 BTU'S
  
 THE GAS DRAWING SUBMITTED FOR THIS PERMIT SHOWS THE
 FOLLOWING BTU VALUES:
 POOL HEATER - 125,000 BTU'S
 DRYER - 22,000 BTU'S
 FIRELOGS - 32,000 BTU'S
 GENERATOR - 387,000 BTU'S
 NEW STOVE - 145,000
 WATER HEATER??? WHERE IS THE BTU LOAD?
 TOTAL BTU LOAD - 711,000 ??
  
 SUBMIT INFORMATION AS TO WHERE YOU OBTAINED THE BTU
 LOADS OF THE GAS APPLIANCES SHOWN ON YOUR DRAWINGS.
 THERE IS QUITE A DISCREPANCY IN THE LOADS OF APPLIANCES
 ON YOUR DRAWING. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.3.
 2) THE 3/4 INCH LINE TO THE NEW STOVE IS UNDERSIZED PER
 TABLE 402.4(2). THE MAXIMUM BTU LOAD ON A 3/4 INCH LINE
 AT 60 FEET IS 137,000 BTU'S.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE
 THAT SHOWS THE CORRECT BTU LOAD. THE BURNERS ADD UP TO
 62,200 BTU'S. WHAT IS THE BTU LOAD OF THE OVEN? THE GAS
 PLAN THAT HAS BEEN SUBMITTED SHOWS THE STOVE AT 145,000
 BTU'S. CLARIFY.
 4) THE STOVE SHALL BE LISTED AND LABELED PER 2017 FBC-
 FUEL GAS SEC.301.3. THE SUBMITTED SPECIFICATIONS DO NOT
 SHOW THIS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW