Plan Review Notes For Permit 19051192 |
Permit Number |
19051192 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-24 09:59:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SITE PLAN DOES NOT INDICATE THE TYPE OF ROAD | | BLOCKS/BARRICADES THAT WILL BE USED. | | | | THE BARRICADES MUST BE MOVEABLE FORE EMERGENCY | | APPARATUS AND RESPONDER ACCRESS. | | | | | | | | 2) THERE ARE NO INDICATIONS OF FIRE LANES ALONG | | CLEMATIS THAT EMERGENCY APPARATUS CAN USE IN THE EVENT | | OF AN INCIDENT | | | | THERE MUST BE A MINIMUM OF HALF THE ROADWAY WIDTH FOR | | TRAVEL, ANYTHING THAT OBSTRUCTS THE TRAVEL ATH MUSBT BE | | IMMEDIATELY MOVEABLE. | | | | | | 3) PLEASE PROVIDE DETAILS ON THE RESUBMITTAL. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|