Plan Review Notes For Permit 19050941 |
Permit Number |
19050941 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-07-16 09:52:16 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE PAGE 13, A .9 FACTOR IS TO BE APPLIED TO SHUTTER | | SPACING IF THE EDGE DISTANCE IS LESS THAN 3.5"; REVISE | | INSTALLATION SCHEDULE ACCORDINGLY. | | | | 2. MOUNTING TYPE WW WAS SPECIFIED; ON THE PRODUCT | | APPROVAL THAT IS FOR WOOD SUBSTRATE. SEE PAGE 12, | | MOUNTING TYPES A AND D WERE CIRCLED. REVISE | | INSTALLATION SCHEDULE. | | | | 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | |
|