Plan Review Notes
Plan Review Notes For Permit 19050941
Permit Number 19050941
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-21 09:54:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING
 ISSUES, FBC R 301:
  
 1. SEE SHEET 13 OF THE PRODUCT APPROVAL; AN EDGE
 DISTANCE OF 3" REQUIRES A .78 FACTOR APPLIED TO THE
 ANCHOR SPACING SPECIFIED IN THE CHARTS.
  
 2. THE SHUTTER SPAN FOR ACCORDIONS SHOULD BE THE BLADE
 LENGTH. SEE OPENING 1, 108 X 64; 115" IS SPECIFIED AS
 SHUTTER SPAN. OPENING 3, 27X64 SPECIFIES 34". PLEASE
 REVISE.
  
 3. CONNECTION TYPE SPECIFIED IS W, BUT THAT IS FOR WOOD
 SUBSTRATE AND MOUNTING TYPES A, D, AND I ARE CIRCLED ON
 SHEETS 12, 14.
  
  