Plan Review Notes
Plan Review Notes For Permit 19050898
Permit Number 19050898
Review Stop Z
Sequence Number 2
Notes
Date Text
2019-10-16 17:03:08SECTION 94-113:
  
 ALL PARKING LOTS SHALL COMPLY WITH LUX AND CANDLE POWER
 REQUIREMENTS IN EXHIBIT A IN SECTION 86-294 :
 MINIMUM HORIZONTAL ILLUMINANCE ON FLOOR: 5 LUX OR 0.5
 FOOTCANDLE
 UNIFORMITY RATIO - 15:1
 MINIMUM VERTICAL ILLUMINANCE AT FIVE FEET ABOVE FLOOR:
 2.5 LUX OR 0.25 FOOTCANDLE
  
 PLEASE INDICATE COMPLIANCE WITH EACH OF THE
 REQUIREMENTS -
 PLEASE INDICATE WHERE MEASUREMENT IS TAKEN WITHIN
 PARKING LOT
  
 PROPERTY LINE MINIMUM DOES NOT MEET REQUIREMENTS -
 PLEASE INCLUDE LIGHTING FROM PUBLIC SOURCES IN
 PHOTOMETRICS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  