Plan Review Notes For Permit 19050879 |
Permit Number |
19050879 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-02 09:57:23 | 1) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW | | PREVENTERWPB AMEND. TO FBC SEC. 105.1. | | 2) THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY | | OF WPB CROSS CONNECTION CONTROL MANUAL. | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS SHOWING THIS DEVICE IS APPROVED FOR | | INSTALLATION IN THE VERTICAL POSITION. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 4) SUBMIT A NARRATIVE EXPLAINING WHY ONLY A PORTION OF | | THE FIRST FLOOR OF THE STRUCTURE IS BEING SPRINKLERED. | | SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE | | OMISSION IS PERMITTED PER 2013 NFPA 13 D SECS. 8.3.2 & | | 8.3.8. NFPA 13D SEC. 8.3. | | 5) SHT. FP-1 - GENERAL NOTE #1 AND SCOPE OF WORK NOTE | | STATES THAT THIS IS AN EXISTING CONGREGATE HOUSING | | FACILITY YET THE PLANS NOTE THIS AS A BIRTHING CENTER. | | CLARIFY. | | 6) A SINGLE CONTROL VALVE ARRANGED TO SHUT OFF BOTH THE | | DOMESTIC SYSTEM AND THE SPRINKLER SYSTEM SHALL BE | | INSTALLED UNLESS A SEPARATE SHUTOFF VALVE FOR THE | | SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE WITH NFPA | | 13D SEC. 7.1.2. NFPA 13D SEC. 7.1.1. | | 7) A WARNING SIGN COMPLYING WITH NFPA 13D SHALL BE | | INSTALLED ADJACENT TO THE MAIN SHUTOFF VALE. NFPA 13D | | SEC.6.3.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|