Plan Review Notes
Plan Review Notes For Permit 19050879
Permit Number 19050879
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-02 09:57:231) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTERWPB AMEND. TO FBC SEC. 105.1.
 2) THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY
 OF WPB CROSS CONNECTION CONTROL MANUAL.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING THIS DEVICE IS APPROVED FOR
 INSTALLATION IN THE VERTICAL POSITION. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SUBMIT A NARRATIVE EXPLAINING WHY ONLY A PORTION OF
 THE FIRST FLOOR OF THE STRUCTURE IS BEING SPRINKLERED.
 SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE
 OMISSION IS PERMITTED PER 2013 NFPA 13 D SECS. 8.3.2 &
 8.3.8. NFPA 13D SEC. 8.3.
 5) SHT. FP-1 - GENERAL NOTE #1 AND SCOPE OF WORK NOTE
 STATES THAT THIS IS AN EXISTING CONGREGATE HOUSING
 FACILITY YET THE PLANS NOTE THIS AS A BIRTHING CENTER.
 CLARIFY.
 6) A SINGLE CONTROL VALVE ARRANGED TO SHUT OFF BOTH THE
 DOMESTIC SYSTEM AND THE SPRINKLER SYSTEM SHALL BE
 INSTALLED UNLESS A SEPARATE SHUTOFF VALVE FOR THE
 SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE WITH NFPA
 13D SEC. 7.1.2. NFPA 13D SEC. 7.1.1.
 7) A WARNING SIGN COMPLYING WITH NFPA 13D SHALL BE
 INSTALLED ADJACENT TO THE MAIN SHUTOFF VALE. NFPA 13D
 SEC.6.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  