Plan Review Notes For Permit 19050879 |
Permit Number |
19050879 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-28 14:18:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) UNDER WHAT CODE ARE YOU PROVIDING PROTECTION OF ONLY | | A PORTION OF THE 1ST FLOOR? | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 2) THE SUBMITTAL SHOWS CONNECTION TO THE DOMESTIC LINE. | | | | IF THIS CONNECTION OFF OA AN EXISTING LINE AND METER OR | | ONE SPECIFICALLY DESIGNATED AS A FIRE LINE? | | | | A SEPARATE DESIGNATED FIRE LINE WITH ITS OWN METER IS | | REQUIRED. | | | | PLEASE PROVIDE DETAILS, | | | | | | | | 3) THIS PLAN IS BEING SENT TO THE BUILDING REVIEW AS | | THEIR COMMENTS ARE QUITE EXTENSIVE AND I WANT TO ENSURE | | THIS DESING MEETS THEIR COMMENTS. | | | | | | 4) THIS PLAN IS BEING SENT TO ENGINEERING FOR THEIR | | COMMENTS ON A SEPARATE DESIGNATED FIRE LINE AND METER. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|