Date |
Text |
2019-08-04 10:08:59 | 1) TWO DIFFERENT DETAILS HAVE BEEN SUBMITTED FOR THE |
| ENCLOSURE OF THE GAS LINE THROUGH THE STAIRWELL.ONE |
| DETAIL IS SIGNED AND SEALED BY AN ARCHITECT AND SHOWS A |
| RATED SOFFIT AND ANOTHER IS DONE BY BUCKEYE PLUMBING |
| SHOWING BASICALLY A RATED BOX BEAM. I HAVE NO IDEA |
| WHICH DETAIL IS TO BE USED. THE DETAIL TO BE USED SHALL |
| BE SIGNED AND SEALED BY AN ARCHITECT. THE |
| ENCLOSURE/SOFFIT SHALL HAVE A MINIMUM FIRE RESISTAVE |
| RATING OF 2 HOURS. 2017 FBC SEC. 1023.2. |
| 2) INDICATE THE SPACING OF THE STUDS ON THE DETAIL FOR |
| THE SOFFIT. WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) THE PLANS DONE BY THE ARCHITECT SHOW AN EXISTING |
| RAIN WATER LEADER IN THIS SAME STAIRWELL. THIS MAY ALSO |
| NEED TO BE ADDRESSED. |
| 4) SHOW THE SOFFIT DIMENSIONS ( LXWXH) ON THE DRAWING |
| BY MNA ARCHITECTS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 5) THE DRAWING BY MNA ARCHITECTS DOES NOTE THE REQUIRED |
| 2 HOUR FIRE RESISTANCE RATING OF THE SOFFIT.THIS MUST |
| BE NOTED ON THE PLANS. |
| 6) SHOW THE CLEAR HEIGHT DIMENSION FROM THE FLOOR TO |
| THE BOTTOM OF THE SOFFIT. THE DISTANCE SHALL BE NOT |
| LESS THAN 7 FEET 6 INCHES PER 2017 FBC SEC.1003.2. |
| 7) SUBMIT THE LISTED FIRE SAFING ASSEMBLY DETAILS FOR |
| SEALING THE PIPE PENETRATIONS THROUGH THE STAIR AND THE |
| SOFFIT.2017 FBC SEC. 714. |
| 8) JOINTS IN THE LAYERED WALLBOARD SHALL BE STAGGERED |
| IN RELATION TO LAYERS BELOW. |
| 9) INDICATE ON THE PLANS HOW THE METAL TRACK STUDS WILL |
| BE ATTACHED TO THE CONCRETE. SHOW TYPE, LENGTH, |
| DIAMETER AND SPACING OF FASTENERS ON THE PLANS. |
| 10) A BUILDING PERMIT WILL BE REQUIRED FOR THE SOFFIT |
| BY A BUILDING CONTRACTOR AND ALSO A FIRE SPRINKLER |
| PERMIT FOR THE WORK BEING DONE TO THE EXISTING FIRE |
| LINE BY A CATEGORY I OR II FIRE PROTECTION CONTRACTOR. |
| . |
| 11) THE DETAIL FROM BUCKEYE NOTES THE BOX BEAM TO BE |
| SELF SUSPENDED. THIS WILL HAVE TO BE VERIFIED BY AN |
| ARCHITECT DUE TO THE LENGTH OF THE BEAM AND WEIGHT OF |
| THE MATERIAL ATTACHED IF THIS DESIGN IS TO BE USED. |
| 12) THE DETAIL FROM BUCKEYE SHALL SPECIFY THE TYPE OF |
| SCREWS TO BE USED.WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| NOTE: PLEASE CALL THIS REVIEWER TO DISCUSS THESE |
| COMMENTS BEFORE REBSUBMITTING. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |