Plan Review Notes
Plan Review Notes For Permit 19050872
Permit Number 19050872
Review Stop G
Sequence Number 2
Notes
Date Text
2019-08-04 10:08:591) TWO DIFFERENT DETAILS HAVE BEEN SUBMITTED FOR THE
 ENCLOSURE OF THE GAS LINE THROUGH THE STAIRWELL.ONE
 DETAIL IS SIGNED AND SEALED BY AN ARCHITECT AND SHOWS A
 RATED SOFFIT AND ANOTHER IS DONE BY BUCKEYE PLUMBING
 SHOWING BASICALLY A RATED BOX BEAM. I HAVE NO IDEA
 WHICH DETAIL IS TO BE USED. THE DETAIL TO BE USED SHALL
 BE SIGNED AND SEALED BY AN ARCHITECT. THE
 ENCLOSURE/SOFFIT SHALL HAVE A MINIMUM FIRE RESISTAVE
 RATING OF 2 HOURS. 2017 FBC SEC. 1023.2.
 2) INDICATE THE SPACING OF THE STUDS ON THE DETAIL FOR
 THE SOFFIT. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE PLANS DONE BY THE ARCHITECT SHOW AN EXISTING
 RAIN WATER LEADER IN THIS SAME STAIRWELL. THIS MAY ALSO
 NEED TO BE ADDRESSED.
 4) SHOW THE SOFFIT DIMENSIONS ( LXWXH) ON THE DRAWING
 BY MNA ARCHITECTS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) THE DRAWING BY MNA ARCHITECTS DOES NOTE THE REQUIRED
 2 HOUR FIRE RESISTANCE RATING OF THE SOFFIT.THIS MUST
 BE NOTED ON THE PLANS.
 6) SHOW THE CLEAR HEIGHT DIMENSION FROM THE FLOOR TO
 THE BOTTOM OF THE SOFFIT. THE DISTANCE SHALL BE NOT
 LESS THAN 7 FEET 6 INCHES PER 2017 FBC SEC.1003.2.
 7) SUBMIT THE LISTED FIRE SAFING ASSEMBLY DETAILS FOR
 SEALING THE PIPE PENETRATIONS THROUGH THE STAIR AND THE
 SOFFIT.2017 FBC SEC. 714.
 8) JOINTS IN THE LAYERED WALLBOARD SHALL BE STAGGERED
 IN RELATION TO LAYERS BELOW.
 9) INDICATE ON THE PLANS HOW THE METAL TRACK STUDS WILL
 BE ATTACHED TO THE CONCRETE. SHOW TYPE, LENGTH,
 DIAMETER AND SPACING OF FASTENERS ON THE PLANS.
 10) A BUILDING PERMIT WILL BE REQUIRED FOR THE SOFFIT
 BY A BUILDING CONTRACTOR AND ALSO A FIRE SPRINKLER
 PERMIT FOR THE WORK BEING DONE TO THE EXISTING FIRE
 LINE BY A CATEGORY I OR II FIRE PROTECTION CONTRACTOR.
 .
 11) THE DETAIL FROM BUCKEYE NOTES THE BOX BEAM TO BE
 SELF SUSPENDED. THIS WILL HAVE TO BE VERIFIED BY AN
 ARCHITECT DUE TO THE LENGTH OF THE BEAM AND WEIGHT OF
 THE MATERIAL ATTACHED IF THIS DESIGN IS TO BE USED.
 12) THE DETAIL FROM BUCKEYE SHALL SPECIFY THE TYPE OF
 SCREWS TO BE USED.WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: PLEASE CALL THIS REVIEWER TO DISCUSS THESE
 COMMENTS BEFORE REBSUBMITTING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW