2019-08-05 10:32:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) A 2HR WALL CHASE IS INDICATED BUT NO "LISTED" WALL
 DIAGRAM SHOWING CONSTRUCTION FEATURES TO MEET THAT
 RATING.
  
 PLEASE PROVIDE A LISTED WALL DETAIL.
  
  
 2) FIRE SPRINKLER WORK IS INDICATED.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  