Plan Review Notes For Permit 19050872 |
Permit Number |
19050872 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-05 10:32:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) A 2HR WALL CHASE IS INDICATED BUT NO "LISTED" WALL | | DIAGRAM SHOWING CONSTRUCTION FEATURES TO MEET THAT | | RATING. | | | | PLEASE PROVIDE A LISTED WALL DETAIL. | | | | | | 2) FIRE SPRINKLER WORK IS INDICATED. | | | | ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE | | PERMIT AND SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN | | APPLICABLE NOTE OF ACKNOWLEDGEMENT. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|