Date |
Text |
2020-01-03 14:09:08 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| FBC M = FBC MECHANICAL |
| |
| BUILDING REVIEW DENIED: |
| |
| THE ISSUES POINTED OUT BY THE BUILDING OFFICIAL HAVE |
| NOT BEEN ADDRESSED. |
| PLEASE SEE (BELOW) COPY OF THE CONCERNS FROM THE |
| BUILDING OFFICIAL (ROBERT BROWN) SENT OUT TO RICHARD |
| ANDERSON BY EMAIL ON JUNE 14, 2019 AND HAVE THEM |
| ADDRESSED BY THE ENGINEER OF RECORD. |
| |
| SUBJECT: RE: PERMIT #18060021 AND REVISION #19050782 |
| |
| HELLO RICHARD, |
| |
| YOU HAVE REQUESTED A MEETING ON SITE. AS NONE OF THE |
| PROPOSED ATTENDEES ARE ENGINEERS, SUCH A MEETING WOULD |
| NOT BE PRODUCTIVE UNTIL WE GET A RESPONSE FROM YOUR |
| ENGINEER ON THE FOLLOWING FUNDAMENTAL DETAILS THAT ARE |
| MISSING FROM THE ENGINEER?S PLAN SHEET S-1. IN FACT |
| HAVING THE ENGINEER ANSWER THESE QUESTIONS WOULD MAKE |
| THE MEETING UNNECESSARY BECAUSE WE COULD THEN PASS THE |
| PLANS AND DO THE INSPECTIONS. |
| |
| I SEE THAT DOUG HARVEY, ASSISTANT BUILDING OFFICIAL, |
| DID THE INSPECTION ON 8/24/18 AND ENTERED THE NOTES |
| THAT YOU INCLUDED IN YOUR EMAIL. I TRUST THAT YOU AND |
| YOUR STRUCTURAL ENGINEER (MASOOD HAJALI) HAVE REVIEWED |
| THE ORIGINALLY PERMITTED PLANS AND ELEVATOR |
| MANUFACTURER?S SPECIFICATION AND CAN SEE WHAT |
| INFORMATION IS NEEDED FORM YOUR ENGINEER BECAUSE IT IS |
| NOT INCLUDED IN THE ARCHITECT?S (NADER GOUBRAN) PLAN, |
| OR THE ELEVATOR MANUFACTURER?S SPEC SHEETS. I HAVE |
| LOOKED AT THE DOCUMENTS AND I FIND THAT THE ARCHITECTS? |
| PLAN (SEE SCREEN SHOT BELOW) SIMPLY STATES THAT THE |
| ELEVATOR LOAD CALCULATIONS WILL BE ENGINEERED PROVIDED |
| ?BY OTHERS?, AND I HAVE ALSO LOOKED AT YOUR ENGINEER?S |
| PLANS SUBMITTED UNDER REVISION #19050782. |
| |
| LOOKING AT ALL THE DOCUMENTS THAT WE HAVE, I CAN SEE |
| THAT THE FOLLOWING NEED TO BE ADDRESSED BY HAVING YOUR |
| ENGINEER SUBMIT ADDITIONAL DETAILS: |
| |
| POINT LOAD - THE ELEVATOR MANUFACTURER ADDRESSES THE |
| REQUIRED SUPPORT AS A DISTRIBUTED LOAD INSTEAD OF A |
| POINT LOAD, AND THAT IS OK, BUT THEIR SPECIFICATION |
| STATES THAT THE FLOOR MUST BE ABLE TO SUPPORT 15 PSI |
| (DRAWING D-PVE-KR-01 INSTALLATION SHEET AND |
| SPECIFICATION SHEET ). THAT IS THE EQUIVALENT OF 2,160 |
| PSF, WHICH EXCEEDS TYPICAL FLOOR SLAB LOADING. THE |
| MANUFACTURER?S SPECIFICATION IS NOT VERY CLEAR, BUT IT |
| WOULD APPEAR THAT THE LOADING WILL BE LOCALIZED AT FOUR |
| COLUMNS WITHIN THE ELEVATOR CYLINDER. YOUR ENGINEER?S |
| PLANS DO NOT ADDRESS THE REQUIRED SUPPORT LOADING AT |
| ALL. WE WILL REQUIRE STRUCTURAL ENGINEERING |
| CALCULATIONS AND DETAILS TO SHOW HOW THE ELEVATOR CAN |
| BE SAFELY SUPPORTED BY THE FLOOR SLAB. |
| |
| ATTACHMENT TO FLOOR - THE ELEVATOR MANUFACTURER |
| SPECIFICATION DOES NOT STATE HOW THE ELEVATOR IS TO BE |
| ANCHORED TO THE SLAB TO STOP IS FROM SHIFTING AND/OR |
| VIBRATING ON THE SLAB. AGAIN, YOUR ENGINEER?S PLANS DO |
| NOT ADDRESS THIS AT ALL. |
| |
| ATTACHMENT TO MID RAIL - THE ELEVATOR MANUFACTURER |
| SPECIFICATION (DRAWING D-TYP-H-04 MOUNTING OPTIONS |
| SHEET) STATES THAT THE ?BALCONY BAND? SHOULD BE A 2? |
| WIDE STEEL STRAP OR ?EQUAL OR GREATER SUBSTITUTE?. YOUR |
| ENGINEER?S PLAN SHOWS THE SUBSTITUTE AS ?? DIA. CABLE |
| STRAP ?BY MANUFACTURER?. THE MANUFACTURER HAS NOT |
| SPECIFIED ?? DIA. CABLE STRAP AND HAS NOT STATED THAT |
| THE EXTERNAL CYLINDER OF THE ELEVATOR CAN WITHSTAND THE |
| APPLIED RESTRAINT PRESSURE FROM A ?? DIA. CABLE WHICH |
| WILL BE MORE THAN FOUR TIMES THE PRESSURE THAT WOULD BE |
| APPLIED BY THE RECOMMENDED 2? WIDE STEEL STRAP. THE |
| ENGINEER WOULD HAVE TO JUSTIFY THE SUBSTITUTION BY |
| LOOKING AT THE CRUSHING PRESSURE DUE TO USING A ?? DIA. |
| CABLE INSTEAD A 2? WIDE STEEL STRAP WHICH HAS MUCH MORE |
| CONTACT AREA AGAINST THAT ELEVATOR CYLINDER. |
| |
| WOOD LANDING - THE ENGINEER?S PLAN SHEET S-1 SHOWS A |
| NEW WOOD LANDING CANTILEVERED UP TO 16? OFF THE EDGE OF |
| THE EXISTING SLAB WITH THE ?WOOD HEADER? HAVING ONLY |
| ONE SCREW AT MID-DEPTH ATTACHING IT TO THE EDGE OF THE |
| SLAB, AND THE WOOD ?RAFTERS? (WHICH ARE ACTUALLY |
| CANTILEVERS) ARE NOT EVEN POSITIVELY ATTACHED TO THE |
| ?WOOD HEADER?. THE ENGINEER?S DETAIL D3 SHOWS THEM |
| SIMPLY SITTING IN AN UNSPECIFIED ?SIMPSON BRACKET? THAT |
| IS SHOWN AS A JOIST HANGER. A CANTILEVER STRUCTURE |
| CANNOT BE SUPPORTED BY JOIST HANGERS BECAUSE SUCH |
| HANGERS ARE ONLY DESIGNED FOR GRAVITY LOAD, NOT |
| CANTILEVER MOMENT LOAD. |
| |
| GUARDRAIL FOR NEW LANDING - THE ENGINEER SHALL ADD MORE |
| INFORMATION TO DETAIL D1 AND D2 TO SHOW HOW THE |
| GUARDRAIL IS SUPPORTED FROM THE WOOD LANDING. THE WOOD |
| LANDING AS CURRENTLY DETAILED DOES NOT APPEAR TO BE |
| CAPABLE OF SUPPORTING THE GUARDRAIL AND THE LOADS AT |
| WOULD BE INDUCED BY PEOPLE LEANING ON THE GAURDRAIL |
| |
| |
| |
| |
| |
| |
| |
| |
| REGARDS, |
| |
| ROBERT BROWN, CBO |
| BUILDING OFFICIAL / BUILDING DIVISION MANAGER |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES DEPARTMENT ? BUILDING DIVISION |
| (561) 805 6652 |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| HTTP://WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSE |
| RVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |