Plan Review Notes
Plan Review Notes For Permit 19050782
Permit Number 19050782
Review Stop B
Sequence Number 2
Notes
Date Text
2020-01-03 14:09:08***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 THE ISSUES POINTED OUT BY THE BUILDING OFFICIAL HAVE
 NOT BEEN ADDRESSED.
 PLEASE SEE (BELOW) COPY OF THE CONCERNS FROM THE
 BUILDING OFFICIAL (ROBERT BROWN) SENT OUT TO RICHARD
 ANDERSON BY EMAIL ON JUNE 14, 2019 AND HAVE THEM
 ADDRESSED BY THE ENGINEER OF RECORD.
  
 SUBJECT: RE: PERMIT #18060021 AND REVISION #19050782
  
 HELLO RICHARD,
  
 YOU HAVE REQUESTED A MEETING ON SITE. AS NONE OF THE
 PROPOSED ATTENDEES ARE ENGINEERS, SUCH A MEETING WOULD
 NOT BE PRODUCTIVE UNTIL WE GET A RESPONSE FROM YOUR
 ENGINEER ON THE FOLLOWING FUNDAMENTAL DETAILS THAT ARE
 MISSING FROM THE ENGINEER?S PLAN SHEET S-1. IN FACT
 HAVING THE ENGINEER ANSWER THESE QUESTIONS WOULD MAKE
 THE MEETING UNNECESSARY BECAUSE WE COULD THEN PASS THE
 PLANS AND DO THE INSPECTIONS.
  
 I SEE THAT DOUG HARVEY, ASSISTANT BUILDING OFFICIAL,
 DID THE INSPECTION ON 8/24/18 AND ENTERED THE NOTES
 THAT YOU INCLUDED IN YOUR EMAIL. I TRUST THAT YOU AND
 YOUR STRUCTURAL ENGINEER (MASOOD HAJALI) HAVE REVIEWED
 THE ORIGINALLY PERMITTED PLANS AND ELEVATOR
 MANUFACTURER?S SPECIFICATION AND CAN SEE WHAT
 INFORMATION IS NEEDED FORM YOUR ENGINEER BECAUSE IT IS
 NOT INCLUDED IN THE ARCHITECT?S (NADER GOUBRAN) PLAN,
 OR THE ELEVATOR MANUFACTURER?S SPEC SHEETS. I HAVE
 LOOKED AT THE DOCUMENTS AND I FIND THAT THE ARCHITECTS?
 PLAN (SEE SCREEN SHOT BELOW) SIMPLY STATES THAT THE
 ELEVATOR LOAD CALCULATIONS WILL BE ENGINEERED PROVIDED
 ?BY OTHERS?, AND I HAVE ALSO LOOKED AT YOUR ENGINEER?S
 PLANS SUBMITTED UNDER REVISION #19050782.
  
 LOOKING AT ALL THE DOCUMENTS THAT WE HAVE, I CAN SEE
 THAT THE FOLLOWING NEED TO BE ADDRESSED BY HAVING YOUR
 ENGINEER SUBMIT ADDITIONAL DETAILS:
  
 POINT LOAD - THE ELEVATOR MANUFACTURER ADDRESSES THE
 REQUIRED SUPPORT AS A DISTRIBUTED LOAD INSTEAD OF A
 POINT LOAD, AND THAT IS OK, BUT THEIR SPECIFICATION
 STATES THAT THE FLOOR MUST BE ABLE TO SUPPORT 15 PSI
 (DRAWING D-PVE-KR-01 INSTALLATION SHEET AND
 SPECIFICATION SHEET ). THAT IS THE EQUIVALENT OF 2,160
 PSF, WHICH EXCEEDS TYPICAL FLOOR SLAB LOADING. THE
 MANUFACTURER?S SPECIFICATION IS NOT VERY CLEAR, BUT IT
 WOULD APPEAR THAT THE LOADING WILL BE LOCALIZED AT FOUR
 COLUMNS WITHIN THE ELEVATOR CYLINDER. YOUR ENGINEER?S
 PLANS DO NOT ADDRESS THE REQUIRED SUPPORT LOADING AT
 ALL. WE WILL REQUIRE STRUCTURAL ENGINEERING
 CALCULATIONS AND DETAILS TO SHOW HOW THE ELEVATOR CAN
 BE SAFELY SUPPORTED BY THE FLOOR SLAB.
  
 ATTACHMENT TO FLOOR - THE ELEVATOR MANUFACTURER
 SPECIFICATION DOES NOT STATE HOW THE ELEVATOR IS TO BE
 ANCHORED TO THE SLAB TO STOP IS FROM SHIFTING AND/OR
 VIBRATING ON THE SLAB. AGAIN, YOUR ENGINEER?S PLANS DO
 NOT ADDRESS THIS AT ALL.
  
 ATTACHMENT TO MID RAIL - THE ELEVATOR MANUFACTURER
 SPECIFICATION (DRAWING D-TYP-H-04 MOUNTING OPTIONS
 SHEET) STATES THAT THE ?BALCONY BAND? SHOULD BE A 2?
 WIDE STEEL STRAP OR ?EQUAL OR GREATER SUBSTITUTE?. YOUR
 ENGINEER?S PLAN SHOWS THE SUBSTITUTE AS ?? DIA. CABLE
 STRAP ?BY MANUFACTURER?. THE MANUFACTURER HAS NOT
 SPECIFIED ?? DIA. CABLE STRAP AND HAS NOT STATED THAT
 THE EXTERNAL CYLINDER OF THE ELEVATOR CAN WITHSTAND THE
 APPLIED RESTRAINT PRESSURE FROM A ?? DIA. CABLE WHICH
 WILL BE MORE THAN FOUR TIMES THE PRESSURE THAT WOULD BE
 APPLIED BY THE RECOMMENDED 2? WIDE STEEL STRAP. THE
 ENGINEER WOULD HAVE TO JUSTIFY THE SUBSTITUTION BY
 LOOKING AT THE CRUSHING PRESSURE DUE TO USING A ?? DIA.
 CABLE INSTEAD A 2? WIDE STEEL STRAP WHICH HAS MUCH MORE
 CONTACT AREA AGAINST THAT ELEVATOR CYLINDER.
  
 WOOD LANDING - THE ENGINEER?S PLAN SHEET S-1 SHOWS A
 NEW WOOD LANDING CANTILEVERED UP TO 16? OFF THE EDGE OF
 THE EXISTING SLAB WITH THE ?WOOD HEADER? HAVING ONLY
 ONE SCREW AT MID-DEPTH ATTACHING IT TO THE EDGE OF THE
 SLAB, AND THE WOOD ?RAFTERS? (WHICH ARE ACTUALLY
 CANTILEVERS) ARE NOT EVEN POSITIVELY ATTACHED TO THE
 ?WOOD HEADER?. THE ENGINEER?S DETAIL D3 SHOWS THEM
 SIMPLY SITTING IN AN UNSPECIFIED ?SIMPSON BRACKET? THAT
 IS SHOWN AS A JOIST HANGER. A CANTILEVER STRUCTURE
 CANNOT BE SUPPORTED BY JOIST HANGERS BECAUSE SUCH
 HANGERS ARE ONLY DESIGNED FOR GRAVITY LOAD, NOT
 CANTILEVER MOMENT LOAD.
  
 GUARDRAIL FOR NEW LANDING - THE ENGINEER SHALL ADD MORE
 INFORMATION TO DETAIL D1 AND D2 TO SHOW HOW THE
 GUARDRAIL IS SUPPORTED FROM THE WOOD LANDING. THE WOOD
 LANDING AS CURRENTLY DETAILED DOES NOT APPEAR TO BE
 CAPABLE OF SUPPORTING THE GUARDRAIL AND THE LOADS AT
 WOULD BE INDUCED BY PEOPLE LEANING ON THE GAURDRAIL
  
  
  
  
  
  
  
  
 REGARDS,
  
 ROBERT BROWN, CBO
 BUILDING OFFICIAL / BUILDING DIVISION MANAGER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? BUILDING DIVISION
 (561) 805 6652
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 HTTP://WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSE
 RVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved