2019-06-17 09:33:56 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19050781 |
| ADD: 1550 PALM BEACH LAKES BLVD. |
| CONT: 5 STAR ELECTRICAL CONTRACTOR, LLC |
| TEL: 855-305-7827 |
| E-MAIL: DENIED |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JUNE 17, 2019 |
| ACTION: DENIED |
| |
| 1) PLEASE BE AWARE EITHER A CERTIFIED GENERAL |
| CONTRACTOR, BUILDING CONTRACTOR AND OR A PALM BEACH |
| COUNTY BUILDING CONTRACTOR WITH PALM BEACH COUNTY |
| COMPETENCY LICENSE WILL BE REQUIRED TO SIGN ONTO THIS |
| PERMIT. 5 STAR ELECTRICAL CONTRACTOR, LLC IS WORKING |
| OUT OF THE SCOPE OF THEIR LICENSE WITH THE SETTING OF |
| CASH WRAPS. |
| PART II |
| ELECTRICAL AND ALARM SYSTEM |
| CONTRACTING |
| 489.505?DEFINITIONS |
| |
| |
| 2) 5 STAR ELECTRICAL CONTRACTOR, LLC PERMIT APPLICATION |
| THAT WAS SUBMITTED IS A COPY, NOT AN ORIGINAL. THE |
| SIGNATURES ON THE PERMIT APPLICATION HAVE TO BE |
| ORIGINAL SIGNATURES, NOT A PHOTOCOPY. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION. 105.4 CONDITIONS OF |
| THE PERMIT. THE ISSUANCE OR GRANTING OF A PERMIT SHALL |
| NOT BE CONSTRUED TO BE A PERMIT FOR, OR AN APPROVAL OF, |
| ANY VIOLATION OF ANY OF THE PROVISIONS OF THIS CODE OR |
| OF ANY FEDERAL, STATE OR LOCAL LAWS, ORDINANCES, CODES |
| OR REGULATIONS. |
| |
| 3) ARCHITECTS SIGNATURE AND SEAL: |
| 3A) THE SIGNATURE WITHIN THE ARCHITECTS SEAL IS A |
| PHOTO-COPY. FL ADMIN CODE 61G16.003 (1) ARCHITECTS. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| |
| 3B) THE ARCHITECTS PRINTED NAME DAVID ANTHONY JR. THIEL |
| WITHIN THE SEAL IS DIFFERENT FROM THE WRITTEN NAME J. |
| JAY. FL ADMIN CODE 61G16.003 (1) ARCHITECTS. |
| |
| 3C) WITHIN THE SEAL THE ARCHITECT WHEN SIGNING THEIR |
| NAME TO THE DOCUMENT IS TO DATE THE PLANS WHEN SIGNED. |
| FL. ADMIN. CODE 61G1-16.004 TITLE BLOCK. ARCHITECT. (4) |
| DATE PREPARED. |
| |
| 3D) THE TITLEBLOCK IS MISSING THE ARCHITECTS BUSINESS |
| LICENSE NUMBER THAT SHOULD ALSO BE LISTED WITHIN THE |
| TITLEBLOCK. 61G1-16.004 TITLE BLOCK. ARCHITECT. (2) |
| FIRM LICENSE NUMBER. |
| |
| 4) THE TITLE SHEET T1.0 UNDER THE HEADING RACKING/ |
| FIXTURES STATES THAT NO SEPARATE PERMIT IS REQUIRED. |
| PLEASE REVIEW THE 2017 WEST PALM BEACH AMENDMENTS TO |
| THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| SECTION 105.2 BUILDING (6). NON FIXED AND MOVABLE |
| FIXTURES, CASES, RACKS, AND COUNTERS NOT OVER 5 FEET 9 |
| INCHES IN HEIGHT. |
| WHEN RACK STORAGE IS OVER 5 FOOT 9 INCHES IN HEIGHT A |
| SEPARATE PERMIT APPLICATION AND PLANS ARE REQUIRED. |
| PLEASE NOTE THE CITY HAS NO PROBLEMS WITH THE RACK |
| STORAGE PLANS BEING PART OF THE OVERALL BUILDING SET OF |
| PLANS. |
| |
| 5) STRUCTURAL CALCULATIONS AND REPORT FOR RACK STORAGE |
| PREPARED BY PETER HIGGINS. PLEASE NOTE THE COVERAGE OF |
| THIS REPORT IS SIGNED AND SEALED BUT THERE IS NO INDEX |
| INDICATING HOW MANY PAGES ARE IN THIS REPORT WHICH ARE |
| COVERED BY THE SEAL. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| 05/06/2009. (2)(A) EVERY SHEET OF PLANS, PRINTS AND |
| REPORTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF |
| CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY |
| THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| |
| 6) SHEET F1.0 FIXTURE PLAN HAS 2 ISSUES: |
| |
| 6A) THE WRITTEN PORTION ON THE BOTTOM OF THE SHEET IS |
| HARDLY VISIBLE, THE SHEET NEEDS TO BE REPRODUCED TO BE |
| LEGIBLE. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 6B) THE PLANS ARE DRAWN TO A 1/16 INCH SCALE. 107.2.1.3 |
| QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| PAPER. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 6C) THE FIXTURE PLAN IS SO LIGHT IN COLOR AND LITTLE |
| CONTRAST AS WELL AS 1/16 INCH SCALE IT IS NOT POSSIBLE |
| TO DETERMINE WHAT AREAS THE WORK IS TO OCCUR FOR RACK |
| STORAGE. . WITH THE NEXT PLAN REVIEW CYCLE THERE MAYBE |
| ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS AND |
| INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| 6D) THE FIXTURE PLAN F1.0 NEEDS TO SHOW COMPLIANCE |
| WITH: 61G15-23.002 ENGINEER SEAL SIGNATURE AND DATE |
| SHALL BE AFFIXED. (2) (B) |
| 2. IDENTIFICATION OF THE PROJECT, BY ADDRESS OR BY LOT |
| NUMBER, BLOCK NUMBER, SECTION OR SUBDIVISION AND CITY |
| OR COUNTY. |
| 3. IDENTIFICATION OF THE APPLICABLE BUILDING CODE AND |
| CHAPTER(S) THAT THE DESIGN IS INTENDED TO MEET. |
| 4. IDENTIFICATION OF ANY COMPUTER PROGRAM USED FOR |
| ENGINEERING THE SPECIFICATIONS OR CALCULATIONS. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |