Plan Review Notes
Plan Review Notes For Permit 19050775
Permit Number 19050775
Review Stop G
Sequence Number 1
Notes
Date Text
2019-05-20 15:20:40PLUMBING 1ST REVISION REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 1) PROVIDE MAKE UP AIR FOR THE FIRE PLACE AND RANGE AS
 THE BTU'S HAVE INCREASED FROM EXISTING . 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 2) PROVIDE TANKLESS WATER HEATER AND GAS VENT PIPE
 INSTALLATION MANUAL. FBC 107.2.1
  
 3) PROVIDE DISTANCE THAT THE TANKLESS VENT PIPING IS
 AWAY FROM ANY DOOR OR WINDOW THAT OPEN AND AWAY FROM
 ANY MECHANICAL MAKE UP AIR VENT. FBC 107.2.1
  
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION