Plan Review Notes For Permit 19050710 |
Permit Number |
19050710 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-09-12 13:55:50 | 1) SHT. A3.02 - DETAIL "A" - IF A TROUGH LAVATORY IS | | INSTALLED IN THE MEN'S ROOM, THE LAVATORY AND WALL | | SPOUT SHALL COMPLY WITH THE 2017 FBC-ACCESS. | | SEC.308.2.2. DETAIL "A" SHOWS A TROUGH LAVATORY FIXTURE | | AND DETAIL 4 SHOWS 2 INDEPENDENT WALL HUNG LAVATORIES. | | CLARIFY. | | 2) SHT. A4.01 - DETAIL #3 - THE HEIGHT OF THE LAVATORY | | SPOUT SHALL COMPLY WITH THE 2017 FBC-ACCESS. | | SEC.308.2.2. | | 3) SHT. P2.1.1 - DETAIL #3 - SANITARY ISOMETRIC DRAWING | | - THE ICE BIN SHALL NOT DISCHARGE TO THE GREASE WASTE | | SYSTEM PER THE 2017 FBC-PLUMBING SEC.1003.2. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|