Plan Review Notes For Permit 19050710 |
Permit Number |
19050710 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-08-23 11:10:41 | 1) SHT. P1.1.3 - THE GREASE INTERCEPTOR SIZING | | CALCULATIONS STATE THAT THERE ARE 3,000 GALLONS OF | | GREASE TRAP CAPACITY PROVIDED. SUBMIT DOCUMENTATION | | THAT CONFIRMS THERE IS INDEED THIS AMOUNT OF CAPACITY | | AVAILABLE IN THE EXISTING GREASE INTERCEPTOR. WPB | | AMEND. TO FBC SEC.107.2.1. | | 2) SHT. P2.1.1 - INDICATE ON THE SANITARY RISER | | DIAGRAMS WHICH ONES ARE CONNECTING TO THE SANITARY | | SYSTEM AND WHICH ONES ARE CONNECTING TO THE GREASE | | WASTE SYSTEM. WASTES THAT DO NOT REQUIRE TREATMENT OR | | SEPARATION SHALL NOT DISCHARGE INTO ANY INTERCEPTOROR | | SEPARATOR. FBC_PLUMBING SEC.1003.2. | | 3) SHT. P1.1.3 - SIZING CALCULATIONS FOR THE GREASE | | INTERCEPTOR CAPACITY SHALL COMPLY WITH THE STANDARDS | | LISTED IN FBC-PLUMBING SEC.1003.3.4. THE INFORMATION ON | | THE PLANS ALSO REFER TO MDC REGULATIONS. WHAT IS THIS | | REFERENCED STANDARD? THIS IS NOT A RECOGNIZED | | STANDARD/REGULATION IN THE FBC-PLUMBING,CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|