| BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- LIFE SAFETY SHEET ALS1.1: |
| A)PROVIDE THE OCCUPANT LOAD ON EACH ROOM OR SPACE. AS |
| REQUIRED BY SEC. 1004.1.1 AND TABLE 1004.1.2 |
| FBC-BUILDING. FOR EXAMPLE PROVIDE THE OCCUPANT LOAD AT |
| PRIVATE DINING #1, PRIVATE DINING #2, BOOTHS, BARS, |
| KITCHEN, ETC. |
| NOTE: TAKE INTO CONSIDERATION THE AREAS WITHOUT FIXED |
| SEATING (SEC. 1004.1.2 FBC) AND AREAS WITH FIXED |
| SEATING (SEC. 1004.4 FBC). |
| |
| RESPONSE: |
| (1) NUMBER OF PEOPLE CALCULATED PER SQUARE FOOTAGE AND |
| NUMBER OF SEAT SHOWN ON FLOOR PLAN DON'T MATCH. FOR |
| EXAMPLE CALCULATIONS FOR DINING #1 SAYS 26 PEOPLE BUT |
| PLAN SHOWS 32 SEATS. SAME APPLIES TO DINING #2 AND |
| OTHER AREAS SHOWING THE SEATS. REVISE AS REQUIRED TO |
| MATCH. |
| |
| (2) THERE ARE NO OCCUPANTS SHOWN FOR RAW BAR AREA. |
| |
| B) OK |
| C) OK |
| D) OK |
| E) OK. |
| F) OK. |
| |
| 2-FLOOR PLAN SHEET A1.1.1: |
| |
| A)PROVIDE COMPLETE APPROVED FIRE RATED WALL ASSEMBLY |
| DETAIL BASED ON ANY OF THE METHODS ALLOWED BY SEC. |
| 703.3 FBC-BUILDING FOR THE TENANT SEPARATION WALL. |
| |
| RESPONSE: |
| ONE HOUR FIRE RATED WALL DETAIL 13/A2.0.1 DOESN'T |
| CORRESPOND TO SPECIFIED UL ASSEMBLY NO U415 SPECIFIED |
| ON THIS WALL DETAIL. REVISE AS REQUIRED. PROVIDE WALL |
| ASSEMBLY DETAIL THAT MATCHES SPECIFIED FIRE RATED |
| APPROVED ASSEMBLY. |
| NOTE: ASSEMBLY UL U415 IS TYPICAL WALL SHAFT WALLS. |
| |
| B) OK |
| C) OK |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| ACCESSIBLE DINING SURFACES AT BAR, RAW BAR AND BOOTH |
| AREAS SHOWING COMPLIANCE WITH SEC. 226 FBC |
| ACCESSIBILITY. |
| |
| RESPONSE: |
| PARTIALLY COMPLIED. COUNTERS SHOWN AT RAW BAR AND BAR |
| AREA SEEM TO COMPLY. |
| |
| THE FOLLOWING ARE COMMENTS FOR THE BOOTHS SHOWN ON |
| PLANS. (NOTE: THERE ARE BOOTHS INSIDE THE RESTAURANT |
| AND OUTSIDE THE RESTAURANT): |
| (1)AT LEAST 5 PERCENT OF THE SEATING SPACES SHALL |
| COMPLY WITH SEC. 902 FBC-ACCESSIBILITY AS REQUIRED BY |
| SEC. 226.2 FBC-ACCESSIBILITY. INFORMATION SHOWN DON'T |
| COMPLY WITH THE 5 PERCENT REQUIREMENT. |
| NOTE: TAKE INTO CONSIDERATION NUMBER OF PEOPLE SEATING |
| ON THE BOOTHS. COORDINATE WITH ITEM #1(A) ABOVE. |
| |
| (2)PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR ALL |
| BENCHES (CURVED AND STRAIGHT) SHOWN ON PLANS AS |
| REQUIRED BY SEC. 202.4 FBC-ACCESSIBILITY AND SEC. 903 |
| FBC-ACCESSIBILITY |
| |
| (3) THE SEATING SPACES NEED TO BE DISPERSED. SEC. 226.2 |
| FBC-ACCESSIBILITY. |
| NOTE: THERE ARE CURVED BOOTHS (INSIDE RESTAURANT) AND |
| STRAIGHT BOOTHS (OUTSIDE AND INSIDE THE RESTAURANT). |
| |
| (4)ACCESSIBLE CLEAR SPACE SHOWN BY THE ROUND BOOTHS |
| DON'T SEEM TO WORK AND IT DOESN'T COMPLY WITH SEC. 902 |
| FBC-ACCESSIBILITY. THE WAY IT IS DRAWN IS SHOWS LIKE |
| THE BOOTH IS NOT USABLE. PROVIDE AN SKETCH SHOWING HOW |
| THE BOOTH IS USED WITH A WHEEL CHAIR IN THE MIDDLE AS |
| SHOWN ON PLANS. SEC. 107.2.1.2 CITY AMENDMENTS. |
| NOTE: MAKE SURE EGRESS PATH IS NOT BLOCKED WHEN |
| DESIGNING SEATING COMPLYING WITH SEC. 902 |
| FBC-ACCESSIBILITY. |
| |
| E) OK. |
| |
| 3- OK. |
| |
| 4- MISSING DOOR SCHEDULE AND WALL, FLOOR AND FINISH |
| SCHEDULES, INTERIOR DESIGN DRAWINGS, SEC. 107.3.5.1.1 |
| CITY AMENDMENTS. |
| |
| RESPONSE: |
| KITCHEN DOUBLE ENTRY DOORS (#112). AT LEAST ONE LEAF |
| NEEDS TO PROVIDE A CLEAR WIDTH OF 32" MINIMUM AS |
| REQUIRED BY SEC. 404.2.2 FBC-ACCESSIBILITY. REVISE AS |
| REQUIRED. |
| |
| 5- OK. |
| |
| 6- OK. |
| |
| 7-OK. |
| |
| 8- ARCHITECT SPECIFIED ON LIFE SAFETY PLAN SHEET ALS1.1 |
| THAT THIS IS A TYPE IIA CONSTRUCTION. ACCORDING TO |
| TABLE 601 FBC-BUILDING TYPE IIA CONSTRUCTION REQUIRES 1 |
| HOUR FIRE RESISTANCE ON THE PRIMARY STRUCTURAL FRAME. |
| DETAIL 8/A2.0.1 NEEDS TO BE REVISED. THE COLUMN NEEDS |
| TO BE FIRE RATED TO THE BOTTOM OF THE UNDERSIDE OF THE |
| STRUCTURAL CEILING ABOVE. THIS DETAIL SPECIFIES FIRE |
| RATING UP TO 6" ABOVE SUSPENDED CEILING. REVISE AS |
| REQUIRED AND PROVIDE DETAILS/SPECS FOR AN APPROVED |
| ASSEMBLY TO FIRE RATE COLUMNS AS REQUIRED BY SEC. 704.1 |
| FBC-BUILDING. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |