2019-05-28 11:23:18FAILED
  
 1) SHEET M2.1.1 LISTS 12 HVAC KEY NOTES INCLUDING "NEW
 CHW FCU"; HOWEVER, THERE IS NO LOCATION SHOWN FOR THIS
 EQUIPMENT ON THE MECHANICAL ROOF PLAN. PLEASE EXPLAIN
 THIS DISCREPANCY.
  
 2) IF THERE IS NEW EQUIPMENT BEING INSTALLED ON THE
 ROOF. IN ACCORDANCE WITH THE CITYPLACE DRI, PLEASE
 PROVIDE VERIFICATION THAT ALL ROOFTOP MECHANICAL
 EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS
 PUBLIC AND PRIVATE UTILITY SERVICE CONNECTIONS;
 HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]