Plan Review Notes
Plan Review Notes For Permit 19050710
Permit Number 19050710
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-18 12:46:46PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) PROVIDE A COMPLETE EXISTING FLOOR PLAN SHOWING ALL
 EXISTING EQUIPMENT. FBC 107.3.5 AS CITY RECORDS #
 15110078 SHOW A COMPLETE DIFFERENT LAY OUT TO INCLUDE
 THE RESTROOMS.
  
 2) PROVIDE DISTANCE FROM WATER HEATER TO FURTHEST HOT
 WATER OUTLET OF NEW PIPING. IF THE TOTAL DEVELOPED
 LENGTH IS OVER 50' THAN A HOT WATER RETURN SYSTEM SHALL
 BE INSTALL AND INSULATED.FBC P607.2, FBC-ENERGY C404.6.
  
 3) PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS.
 THERE IS NO RECORD OF AN EXISTING INTERCEPTOR. IF ONE
 EXISTS PLEASE PROVIDE INSPECTION REPORT ON CONDITION
 AND SIZE. IF THE INTERCEPTOR IS UNDERSIZED BASED ON
 REQUIREMENTS FBC-P 1003.3.4, 1003.3.4.1 THEN THE
 CORRECT REQUIRED SIZE INTERCEPTOR WILL NEED TO BE
 INSTALLED WITH ITS OWN STANDALONE PERMIT. FBC P 1003.1
  
 4) PROVIDE A COMPLETE SANITARY RISER DRAWING. PROVIDE
 PIPE SIZE OF EXISTING FLOOR SINKS AS YOU CALL OUT
 ADDITIONAL DFU LOAD RUNNING NEW SINKS INTO THEM. FBC
 107.3.5
  
 5) ADD NOTE THAT HAND SINKS SHALL BE TEMPERED BY MEANS
 OF AN APPROVED ASSE 1070 DEVICE. FBC-P 607.1.2
  
 6) PROVIDE BATHROOM FIXTURE DETAIL SHOWING COMPLIANCE
 WITH FLORIDA ACCESSIBILITY. EXAMPLE:GRAB BAR LOCATIONS,
 MIRROR MOUNTING, TOILET PAPER MOUNTING, ETC. PLEASE
 REFER TO CHAPTER 6 PLUMBING FIXTURES FBC-ACCESSIBILITY
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR