2019-06-13 14:43:40 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19050710 |
| 6/13/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1.1.1: SWITCH THE LOCATIONS OF KEYNOTES #2 & |
| 3 ON THE PLANS (CHILLED WATER AND CONDENSATE AT FCU'S)- |
| SECTION 107.2.1 WPB. |
| |
| 2) M1.1.1: PROVIDE AUTOMATIC DAMPERS FOR THE O/A DUCTS |
| SUPPLYING THE NEW FCU'S- SECTION C403.2.4.2 FBC EC. |
| |
| 3) M2.1.1: PROVIDE AN FCU INSTALLATION DETAIL- SECTION |
| 107.2.1 WPB. |
| |
| 4) REFER TO SECTION C403.2.6.1 FBC EC AND INDICATE HOW |
| COMPLIANCE IS BEING MET. |
| |
| C403.2.6.1 DEMAND CONTROLLED VENTILATION. |
| |
| DEMAND CONTROL VENTILATION (DCV) SHALL BE PROVIDED FOR |
| SPACES LARGER THAN 500 SQUARE FEET (46.5 M2) AND WITH |
| AN AVERAGE OCCUPANT LOAD OF 25 PEOPLE PER 1,000 SQUARE |
| FEET (93 M2) OF FLOOR AREA (AS ESTABLISHED IN TABLE |
| 403.3.1.1 OF THE FLORIDA BUILDING CODE, MECHANICAL) AND |
| SERVED BY SYSTEMS WITH ONE OR MORE OF THE FOLLOWING: |
| |
| 1.AN AIR-SIDE ECONOMIZER. |
| |
| 2.AUTOMATIC MODULATING CONTROL OF THE OUTDOOR AIR |
| DAMPER. |
| |
| 3.A DESIGN OUTDOOR AIRFLOW GREATER THAN 3,000 CFM (1416 |
| L/S). |
| |
| EXCEPTION: DEMAND CONTROL VENTILATION IS NOT REQUIRED |
| FOR SYSTEMS AND SPACES AS FOLLOWS: |
| |
| 1.SYSTEMS WITH ENERGY RECOVERY COMPLYING WITH SECTION |
| C403.2.7. |
| |
| 2.MULTIPLE-ZONE SYSTEMS WITHOUT DIRECT DIGITAL CONTROL |
| OF INDIVIDUAL ZONES COMMUNICATING WITH A CENTRAL |
| CONTROL PANEL. |
| |
| 3.SYSTEMS WITH A DESIGN OUTDOOR AIRFLOW LESS THAN 1,200 |
| CFM (566 L/S). |
| |
| 4.SPACES WHERE THE SUPPLY AIRFLOW RATE MINUS ANY MAKEUP |
| OR OUTGOING TRANSFER AIR REQUIREMENT IS LESS THAN 1,200 |
| CFM (566 L/S). |
| |
| 5.VENTILATION PROVIDED FOR PROCESS LOADS ONLY. |
| |
| 6) SUBMIT PRODUCT DATA SHEETS FOR THE NEW GAS-FIRED |
| COOKING APPLIANCES- SECTION 623.1 FBC FG. |
| |
| 7) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE |
| REQUIRED FOR COMMERCIAL KITCHEN HOODS AND FIRE |
| SUPPRSSION SYSTEMS, AND WALK-IN COOLERS AND FREEZERS- |
| SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |