Plan Review Notes
Plan Review Notes For Permit 19050710
Permit Number 19050710
Review Stop M
Sequence Number 1
Notes
Date Text
2019-06-13 14:43:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050710
 6/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.1: SWITCH THE LOCATIONS OF KEYNOTES #2 &
 3 ON THE PLANS (CHILLED WATER AND CONDENSATE AT FCU'S)-
 SECTION 107.2.1 WPB.
  
 2) M1.1.1: PROVIDE AUTOMATIC DAMPERS FOR THE O/A DUCTS
 SUPPLYING THE NEW FCU'S- SECTION C403.2.4.2 FBC EC.
  
 3) M2.1.1: PROVIDE AN FCU INSTALLATION DETAIL- SECTION
 107.2.1 WPB.
  
 4) REFER TO SECTION C403.2.6.1 FBC EC AND INDICATE HOW
 COMPLIANCE IS BEING MET.
  
 C403.2.6.1 DEMAND CONTROLLED VENTILATION.
  
 DEMAND CONTROL VENTILATION (DCV) SHALL BE PROVIDED FOR
 SPACES LARGER THAN 500 SQUARE FEET (46.5 M2) AND WITH
 AN AVERAGE OCCUPANT LOAD OF 25 PEOPLE PER 1,000 SQUARE
 FEET (93 M2) OF FLOOR AREA (AS ESTABLISHED IN TABLE
 403.3.1.1 OF THE FLORIDA BUILDING CODE, MECHANICAL) AND
 SERVED BY SYSTEMS WITH ONE OR MORE OF THE FOLLOWING:
  
 1.AN AIR-SIDE ECONOMIZER.
  
 2.AUTOMATIC MODULATING CONTROL OF THE OUTDOOR AIR
 DAMPER.
  
 3.A DESIGN OUTDOOR AIRFLOW GREATER THAN 3,000 CFM (1416
 L/S).
  
 EXCEPTION: DEMAND CONTROL VENTILATION IS NOT REQUIRED
 FOR SYSTEMS AND SPACES AS FOLLOWS:
  
 1.SYSTEMS WITH ENERGY RECOVERY COMPLYING WITH SECTION
 C403.2.7.
  
 2.MULTIPLE-ZONE SYSTEMS WITHOUT DIRECT DIGITAL CONTROL
 OF INDIVIDUAL ZONES COMMUNICATING WITH A CENTRAL
 CONTROL PANEL.
  
 3.SYSTEMS WITH A DESIGN OUTDOOR AIRFLOW LESS THAN 1,200
 CFM (566 L/S).
  
 4.SPACES WHERE THE SUPPLY AIRFLOW RATE MINUS ANY MAKEUP
 OR OUTGOING TRANSFER AIR REQUIREMENT IS LESS THAN 1,200
 CFM (566 L/S).
  
 5.VENTILATION PROVIDED FOR PROCESS LOADS ONLY.
  
 6) SUBMIT PRODUCT DATA SHEETS FOR THE NEW GAS-FIRED
 COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE
 REQUIRED FOR COMMERCIAL KITCHEN HOODS AND FIRE
 SUPPRSSION SYSTEMS, AND WALK-IN COOLERS AND FREEZERS-
 SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  