2019-06-18 12:20:01 | GAS 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE REVIEW |
| COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN |
| REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF |
| SUBMITTED CORRECTIONS |
| |
| 1) SUBMIT AN COMPLETE ISOMETRIC DRAWING THAT CLEARLY |
| SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 |
| FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. |
| |
| 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL |
| GAS SEC.304.9.3 |
| |
| 3) PROVIDE AN EXISTING FLOOR PLAN SHOWING ALL EXISTING |
| EQUIPMENT. FBC 107.3.5 |
| |
| 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS |
| APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| SEC.305.1. |
| |
| 5) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| SECS. 10.4, 10.5 OF NFPA 96-08. |
| |
| 6) PLEASE NOTE THE TANKLESS WATER HEATER WAS REPLACED |
| IN 2016 UNDER PERMIT#16020422 WITH NO INSPECTIONS. CODE |
| VIOLATIONS MAY EXIST THAT YOU WILL BE REQUIRED TO TAKE |
| CARE OF. |
| |
| |