2019-09-18 10:38:04BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19050683
 REVIEWED: JULY 19, 2019
 2 ND REVIEW: SEPTEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 ADDITIONAL COMMENT:
 IN REVIEWING THE GEOTECHNICAL REPORT IT APPEARS THAT
 THE RECOMMENDATIONS ARE NOT BEING IMPLEMENTED (SEE PAGE
 6 OF 14 IN GEO REPORT).
 ALSO, SEE CODE REQUIRMENTS FOR DEPTH OF FOOTING.
 1809.4 FBC[B] DEPTH AND WIDTH OF FOOTINGS. THE MINIMUM
 DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE
 SHALL BE 12 INCHES. WHERE APPLICABLE, THE REQUIREMENTS
 OF SECTION.
 FOOTER IS SHOWN AT 18 DEEP, BUT IT SHOWS ONLY 8 INCHES
 BELOW GRADE.
 PLEASE REVIEW FOOTER GRADE DEPTH AND PROVIDE RESPONSE
 FOR WHAT IS THE DEPTH OF FOOTER INTO GRADE.
  
 PROVISOS:
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT
 AND DOORS.
 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE
 INSPECTOR PRIOR TO INSTALLATION.
 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF
 APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF.
 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS
 WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE
 SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND
 SITE LIGHTING
 5. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
 IF THERE ARE MORE DEFFERED SUBMITTALS THAN LISTED
 ABOVE, PLEASE PUT IN A RESPONSE AND I WILL ADD THEM TO
 FINAL LIST.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  