2019-09-18 10:38:04 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19050683 |
| REVIEWED: JULY 19, 2019 |
| 2 ND REVIEW: SEPTEMBER 18, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| ADDITIONAL COMMENT: |
| IN REVIEWING THE GEOTECHNICAL REPORT IT APPEARS THAT |
| THE RECOMMENDATIONS ARE NOT BEING IMPLEMENTED (SEE PAGE |
| 6 OF 14 IN GEO REPORT). |
| ALSO, SEE CODE REQUIRMENTS FOR DEPTH OF FOOTING. |
| 1809.4 FBC[B] DEPTH AND WIDTH OF FOOTINGS. THE MINIMUM |
| DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE |
| SHALL BE 12 INCHES. WHERE APPLICABLE, THE REQUIREMENTS |
| OF SECTION. |
| FOOTER IS SHOWN AT 18 DEEP, BUT IT SHOWS ONLY 8 INCHES |
| BELOW GRADE. |
| PLEASE REVIEW FOOTER GRADE DEPTH AND PROVIDE RESPONSE |
| FOR WHAT IS THE DEPTH OF FOOTER INTO GRADE. |
| |
| PROVISOS: |
| - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE |
| PLANS AT FINAL STAMPING. |
| |
| 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT |
| AND DOORS. |
| 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE |
| INSPECTOR PRIOR TO INSTALLATION. |
| 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF |
| APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF. |
| 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS |
| WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE |
| SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND |
| SITE LIGHTING |
| 5. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| |
| IF THERE ARE MORE DEFFERED SUBMITTALS THAN LISTED |
| ABOVE, PLEASE PUT IN A RESPONSE AND I WILL ADD THEM TO |
| FINAL LIST. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |