Plan Review Notes
Plan Review Notes For Permit 19050683
Permit Number 19050683
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-18 10:22:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. C-6 PAVING, DRAINAGE AND GRADING PLAN
 A. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN
 P101, NOTE 8, WHICH INDICATES STORM WATER DISCHARGING
 TO THE SITE STORM.
 2. C-8 UTILITY PLAN
 A. WATER METER AND BACKFLOW PREVENTER ARE LOCATED
 OUTSIDE OF THE PROPERTY IN WHAT APPEARS TO BE THE
 UTILITY EASEMENT. PER WPB CCCM STANDARD DETAIL WS-11,
 BACKFLOW ASSEMBLY SHALL BE LOCATED DIRECTLY AFTER THE
 METER ON PRIVATE PROPERTY OUTSIDE OF THE UTILITY
 EASEMENT. PER WPB FBC 107.2.1, PROVIDE COMPLETE
 CLARIFICATION OF PRIVATE PROPERTY AND PUBLIC EASEMENT.
 B. PER WPB FBC 107.2.1, AT THE GREASE INTERCEPTOR
 LOCATION, ELIMINATE NOTE REFERRING TO PBCWUD STANDARDS
 AND REPLACE WITH NOTE ?SHALL COMPLY WITH CITY OF WPB
 UTILITIES DEPT. STANDARD DETAIL GS-7.?
 C. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN
 P002 WHICH CALLS FOR THREE (3) 1250 GALLON GREASE
 INTERCEPTORS.
 3. REGARDING ALL PBC WUD SHEETS, PLEASE BE ADVISED THAT
 UTILITIES DETAILS SHEETS SHALL BE SUBMITTED WITH THE
 ENGINEER OF RECORD SEAL/STAMP AND SIGNATURE (ELECTRONIC
 CERTIFIED BY A CERTIFICATE AUTHORITY) AND SHALL COMPLY
 WITH WPB PUBLIC UTILITIES REQUIREMENTS. THE FOLLOWING
 COMMENTS CONCERNING PBC WUD SHEETS SHALL BE ADDRESSED
 ON PLANS AS NOTED ABOVE.
 A. PBC WUD SHEET 1 OF 4
 1) DETAIL 7W: PBCWUD IS NOT THE AUTHORITY HAVING
 JURISDICTION IN THE CITY OF WEST PALM BEACH. PER WPB
 FBC 107.2.1, ADD TO NOTE 1 THAT REDUCED PRESSURE
 BACKFLOW PREVENTER ASSEMBLY SHALL COMPLY WITH WPB CCCM
 STANDARD DETAIL WS-11.
 B. PBC WUD SHEET 4 OF 4 (POTABLE WATER DETAILS)
 1) DETAIL 33W/42W: WHAT DO THESE DETAILS PERTAIN TO?
 PER WPB FBC 107.2.1, PLEASE CLARIFY AND SHOW LOCATION
 ON C-8 UTILITY PLAN.
 4. A004 DUMPSTER DETAILS
 A. A FLOOR DRAIN IS SHOWN. WHAT IS THE PURPOSE OF THIS
 DRAIN? PLEASE NOTE THAT IF IT DRAINS TO SANITARY, IT
 WILL ALLOW STORM WATER TO ENTER THE SANITARY WHICH IS
 PROHIBITED. IF THE DRAIN IS TO REMAIN, PROVIDE DETAILS
 AND COORDINATE WITH PLUMBING AND CIVIL. CITY OF WPB
 DOES NOT REQUIRE A FLOOR DRAIN IN THIS STRUCTURE.
 5. A402 ACCESSIBILITY STANDARDS
 A. GRAB BARS SHALL BE 33? TO 36? TO TOP GRIPPING
 SURFACE OF GRAB BAR, NOT TO CENTERLINE PER FBC ACC
 609.3. CORRECT DETAILS 10 AND 5 TO REFLECT THE SAME.
 B. WATER CLOSET SHALL BE 16?MIN/18? MAX CENTER FROM
 SIDE WALL PER FBC ACC 604.2. CORRECT DETAIL 10 AND
 DETAIL 4 TO REFLECT THE SAME.
 6. A501: DETAIL 21; 4? PRIMARY DOWNSPOUT IS INCORRECTLY
 TITLED ?COOLER BASE DETAIL 21?. PER WPB FBC 107.2.1,
 PLEASE CORRECT TO READ ?PRIMARY DOWNSPOUT SECTION
 DETAIL 25?. INDICATE ON DETAIL 25 WHETHER OR NOT STORM
 DISCHARGE IS TO TERMINATE ABOVE GRADE OR CONNECT
 DIRECTLY TO THE SITE STORM WATER. COORDINATE WITH C-6
 PAVING, DRAINAGE AND GRADING PLAN.
 7. PLAN SHEET P101 NOTE 13 AND 14: PROVIDE INSULATION
 OF GREASY WASTE LINES WHICH ARE PROVIDED WITH HEAT
 TRACE
 8. P002 GREASE INTERCEPTOR: REVIEW CITY OF WPB
 UTILITIES DEPT. STANDARD DETAIL GS-7 AND MODIFY
 INTERCEPTOR DETAIL AS APPLICABLE.
 9. P301
 A. DETAIL 15 WATER HEATER; PROVIDE VACUUM RELIEF VALVE
 (VRV) AT COLD WATER SUPPLY IN LIEU OF ATMOSPHERIC
 VACUUM BREAKER (AVB) TO CONFORM TO THE VERBAGE OF FBC
 PL 504.2.
 B. DETAIL 11 IS NOT APPLICABLE. PLEASE REMOVE PER WPB
 FBC 107.2.1.
 9. P001
 A. PLUMBING FIXTURE SCHEDULE CALLS OUT FD (FLOOR DRAIN)
 IN RESTROOMS WITH TRAP PRIMER. P101 AND P201 DO NOT
 SHOW FLOOR DRAINS IN THE RESTROOMS. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
 B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR MIXING
 VALVES AT HAND SINKS AND LAVATORIES
 10. P201, PROVIDE TWO WAY CO DOWNSTREAM OF EACH GREASE
 INTERCEPTOR TO COMPLY WITH CITY OF WPB UTILITIES DEPT.
 STANDARD DETAIL GS-7.
 11. P202
 A. WATER RISER DIAGRAM SEEMS TO INDICATE TRAP PRIMERS
 FOR ALL FLOOR SINKS AND FLOOR DRAINS. PLEASE INDICATE
 THE SAME IN P001 PLUMBING SCHEDULE REMARKS. AT A
 MINIMUM, PER FBC PL 1002.4.1, TRAP SEAL PROTECTION FOR
 THE ANY FLOOR DRAIN AND FOR THE FLOOR SINK SERVING THE
 WATER HEATER IN ROOM #116 IS REQUIRED.
 B. PER WPB FBC 107.2.1, PLEASE IDENTIFY BACKFLOW
 PREVENTERS ON P202 WATER RISER DIAGRAM
 C. PROVIDE FULL OPEN VALVES ON ALL DOWN FEED PIPES PER
 FBC PL 606.1(5).
 12. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR(S).
 13. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER.
 14. P102/NOTE 9 DOES NOT MATCH P103/NOTE 2. PER WPB FBC
 107.2.1, CLARIFY AND CORRECT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050683 1510 BELVEDERE RD
  