Date |
Text |
2019-07-18 10:22:34 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMEMTS: DENIED |
| 1. C-6 PAVING, DRAINAGE AND GRADING PLAN |
| A. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN |
| P101, NOTE 8, WHICH INDICATES STORM WATER DISCHARGING |
| TO THE SITE STORM. |
| 2. C-8 UTILITY PLAN |
| A. WATER METER AND BACKFLOW PREVENTER ARE LOCATED |
| OUTSIDE OF THE PROPERTY IN WHAT APPEARS TO BE THE |
| UTILITY EASEMENT. PER WPB CCCM STANDARD DETAIL WS-11, |
| BACKFLOW ASSEMBLY SHALL BE LOCATED DIRECTLY AFTER THE |
| METER ON PRIVATE PROPERTY OUTSIDE OF THE UTILITY |
| EASEMENT. PER WPB FBC 107.2.1, PROVIDE COMPLETE |
| CLARIFICATION OF PRIVATE PROPERTY AND PUBLIC EASEMENT. |
| B. PER WPB FBC 107.2.1, AT THE GREASE INTERCEPTOR |
| LOCATION, ELIMINATE NOTE REFERRING TO PBCWUD STANDARDS |
| AND REPLACE WITH NOTE ?SHALL COMPLY WITH CITY OF WPB |
| UTILITIES DEPT. STANDARD DETAIL GS-7.? |
| C. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN |
| P002 WHICH CALLS FOR THREE (3) 1250 GALLON GREASE |
| INTERCEPTORS. |
| 3. REGARDING ALL PBC WUD SHEETS, PLEASE BE ADVISED THAT |
| UTILITIES DETAILS SHEETS SHALL BE SUBMITTED WITH THE |
| ENGINEER OF RECORD SEAL/STAMP AND SIGNATURE (ELECTRONIC |
| CERTIFIED BY A CERTIFICATE AUTHORITY) AND SHALL COMPLY |
| WITH WPB PUBLIC UTILITIES REQUIREMENTS. THE FOLLOWING |
| COMMENTS CONCERNING PBC WUD SHEETS SHALL BE ADDRESSED |
| ON PLANS AS NOTED ABOVE. |
| A. PBC WUD SHEET 1 OF 4 |
| 1) DETAIL 7W: PBCWUD IS NOT THE AUTHORITY HAVING |
| JURISDICTION IN THE CITY OF WEST PALM BEACH. PER WPB |
| FBC 107.2.1, ADD TO NOTE 1 THAT REDUCED PRESSURE |
| BACKFLOW PREVENTER ASSEMBLY SHALL COMPLY WITH WPB CCCM |
| STANDARD DETAIL WS-11. |
| B. PBC WUD SHEET 4 OF 4 (POTABLE WATER DETAILS) |
| 1) DETAIL 33W/42W: WHAT DO THESE DETAILS PERTAIN TO? |
| PER WPB FBC 107.2.1, PLEASE CLARIFY AND SHOW LOCATION |
| ON C-8 UTILITY PLAN. |
| 4. A004 DUMPSTER DETAILS |
| A. A FLOOR DRAIN IS SHOWN. WHAT IS THE PURPOSE OF THIS |
| DRAIN? PLEASE NOTE THAT IF IT DRAINS TO SANITARY, IT |
| WILL ALLOW STORM WATER TO ENTER THE SANITARY WHICH IS |
| PROHIBITED. IF THE DRAIN IS TO REMAIN, PROVIDE DETAILS |
| AND COORDINATE WITH PLUMBING AND CIVIL. CITY OF WPB |
| DOES NOT REQUIRE A FLOOR DRAIN IN THIS STRUCTURE. |
| 5. A402 ACCESSIBILITY STANDARDS |
| A. GRAB BARS SHALL BE 33? TO 36? TO TOP GRIPPING |
| SURFACE OF GRAB BAR, NOT TO CENTERLINE PER FBC ACC |
| 609.3. CORRECT DETAILS 10 AND 5 TO REFLECT THE SAME. |
| B. WATER CLOSET SHALL BE 16?MIN/18? MAX CENTER FROM |
| SIDE WALL PER FBC ACC 604.2. CORRECT DETAIL 10 AND |
| DETAIL 4 TO REFLECT THE SAME. |
| 6. A501: DETAIL 21; 4? PRIMARY DOWNSPOUT IS INCORRECTLY |
| TITLED ?COOLER BASE DETAIL 21?. PER WPB FBC 107.2.1, |
| PLEASE CORRECT TO READ ?PRIMARY DOWNSPOUT SECTION |
| DETAIL 25?. INDICATE ON DETAIL 25 WHETHER OR NOT STORM |
| DISCHARGE IS TO TERMINATE ABOVE GRADE OR CONNECT |
| DIRECTLY TO THE SITE STORM WATER. COORDINATE WITH C-6 |
| PAVING, DRAINAGE AND GRADING PLAN. |
| 7. PLAN SHEET P101 NOTE 13 AND 14: PROVIDE INSULATION |
| OF GREASY WASTE LINES WHICH ARE PROVIDED WITH HEAT |
| TRACE |
| 8. P002 GREASE INTERCEPTOR: REVIEW CITY OF WPB |
| UTILITIES DEPT. STANDARD DETAIL GS-7 AND MODIFY |
| INTERCEPTOR DETAIL AS APPLICABLE. |
| 9. P301 |
| A. DETAIL 15 WATER HEATER; PROVIDE VACUUM RELIEF VALVE |
| (VRV) AT COLD WATER SUPPLY IN LIEU OF ATMOSPHERIC |
| VACUUM BREAKER (AVB) TO CONFORM TO THE VERBAGE OF FBC |
| PL 504.2. |
| B. DETAIL 11 IS NOT APPLICABLE. PLEASE REMOVE PER WPB |
| FBC 107.2.1. |
| 9. P001 |
| A. PLUMBING FIXTURE SCHEDULE CALLS OUT FD (FLOOR DRAIN) |
| IN RESTROOMS WITH TRAP PRIMER. P101 AND P201 DO NOT |
| SHOW FLOOR DRAINS IN THE RESTROOMS. PER WPB FBC |
| 107.2.1, PLEASE CLARIFY. |
| B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR MIXING |
| VALVES AT HAND SINKS AND LAVATORIES |
| 10. P201, PROVIDE TWO WAY CO DOWNSTREAM OF EACH GREASE |
| INTERCEPTOR TO COMPLY WITH CITY OF WPB UTILITIES DEPT. |
| STANDARD DETAIL GS-7. |
| 11. P202 |
| A. WATER RISER DIAGRAM SEEMS TO INDICATE TRAP PRIMERS |
| FOR ALL FLOOR SINKS AND FLOOR DRAINS. PLEASE INDICATE |
| THE SAME IN P001 PLUMBING SCHEDULE REMARKS. AT A |
| MINIMUM, PER FBC PL 1002.4.1, TRAP SEAL PROTECTION FOR |
| THE ANY FLOOR DRAIN AND FOR THE FLOOR SINK SERVING THE |
| WATER HEATER IN ROOM #116 IS REQUIRED. |
| B. PER WPB FBC 107.2.1, PLEASE IDENTIFY BACKFLOW |
| PREVENTERS ON P202 WATER RISER DIAGRAM |
| C. PROVIDE FULL OPEN VALVES ON ALL DOWN FEED PIPES PER |
| FBC PL 606.1(5). |
| 12. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| INTERCEPTOR(S). |
| 13. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| PREVENTER. |
| 14. P102/NOTE 9 DOES NOT MATCH P103/NOTE 2. PER WPB FBC |
| 107.2.1, CLARIFY AND CORRECT. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19050683 1510 BELVEDERE RD |
| |