Plan Review Notes
Plan Review Notes For Permit 19050683
Permit Number 19050683
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-18 15:23:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR KITCHEN EQUIPMENT PER FBC FG 304.1
 2. P201
 A. GAS ISOMETRIC
 1) PER WPB FBC 107.2.1, ISOMETRIC DRAWING SHALL CLEARLY
 SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE AND CONFIRM
 THAT SIZING IS IN ACCORDANCE WITH FBC PL 402.4.1,
 402.4.2.
 2) PROVIDE UNION BETWEEN MANUAL VALVE AND THE AUTOMATIC
 SHUT OFF VALVE FOR THE EMERGENCY SHUT DOWN TO THE
 COOKING LINE PER NFPA 96, SECS. 10.4, 10.5.
 B. NOTE 1: PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION
 FOR FLEXIBLE GAS CONNECTORS COMPLYING WITH FBC FG
 411.1.
 3. P301
 A. P301 WATER HEATER DETAIL; RESEARCH OF THE CONCENTRIC
 VENT SEEMS TO INDICATE THAT THIS PRODUCT IS FOR
 SIDEWALL INSTALLATION ONLY. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER AND MODEL # FOR CONCENTRIC VENT
 WITH DOCUMENTATION THAT ALLOWS VERTICAL INSTALLATION
 FOR ROOF PENETRATION AND IS NOT LIMITED TO SIDEWALL
 INSTALLATION. IF SIDEWALL INSTALLATION IS TO BE USED
 THEN PROVIDE LOCATION ON BUILDING WALL AND INCLUDE AN
 ELEVATION DETAIL SHOWING COMPLIANCE WITH FBC FG 502
 THROUGH 505. IF THROUGH THE ROOF VENTING IS TO BE USED
 THEN PROVIDE A DETAIL FOR THAT INSTALLATION SHOWING
 COMPLIANCE WITH FBC FG 502 THROUGH 505. EITHER DETAIL
 SHALL SHOW TYPE, LOCATION, SIZE, TERMINATION POINT,
 HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS
 VENT(S) AS ARE APPLICABLE.
 B. DETAIL 3 SHOWS GAS PIPING ABOVE ROOF. FLOOR PLAN
 SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 C. DETAIL 10 SHOWS GAS PIPING TO ABOVE ROOF. FLOOR PLAN
 SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE
 WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC FG SEC. 402.2, AND 301.3.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050683 1510 BELVEDERE RD
  


Account Summary | Usage Policy | Privacy Policy