| 1ST REVIEW |
| GAS COMMENTS: DENIED |
| 1. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| COMBUSTION AIR KITCHEN EQUIPMENT PER FBC FG 304.1 |
| 2. P201 |
| A. GAS ISOMETRIC |
| 1) PER WPB FBC 107.2.1, ISOMETRIC DRAWING SHALL CLEARLY |
| SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE AND CONFIRM |
| THAT SIZING IS IN ACCORDANCE WITH FBC PL 402.4.1, |
| 402.4.2. |
| 2) PROVIDE UNION BETWEEN MANUAL VALVE AND THE AUTOMATIC |
| SHUT OFF VALVE FOR THE EMERGENCY SHUT DOWN TO THE |
| COOKING LINE PER NFPA 96, SECS. 10.4, 10.5. |
| B. NOTE 1: PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION |
| FOR FLEXIBLE GAS CONNECTORS COMPLYING WITH FBC FG |
| 411.1. |
| 3. P301 |
| A. P301 WATER HEATER DETAIL; RESEARCH OF THE CONCENTRIC |
| VENT SEEMS TO INDICATE THAT THIS PRODUCT IS FOR |
| SIDEWALL INSTALLATION ONLY. PER WPB FBC 107.2.1, |
| PROVIDE MANUFACTURER AND MODEL # FOR CONCENTRIC VENT |
| WITH DOCUMENTATION THAT ALLOWS VERTICAL INSTALLATION |
| FOR ROOF PENETRATION AND IS NOT LIMITED TO SIDEWALL |
| INSTALLATION. IF SIDEWALL INSTALLATION IS TO BE USED |
| THEN PROVIDE LOCATION ON BUILDING WALL AND INCLUDE AN |
| ELEVATION DETAIL SHOWING COMPLIANCE WITH FBC FG 502 |
| THROUGH 505. IF THROUGH THE ROOF VENTING IS TO BE USED |
| THEN PROVIDE A DETAIL FOR THAT INSTALLATION SHOWING |
| COMPLIANCE WITH FBC FG 502 THROUGH 505. EITHER DETAIL |
| SHALL SHOW TYPE, LOCATION, SIZE, TERMINATION POINT, |
| HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS |
| VENT(S) AS ARE APPLICABLE. |
| B. DETAIL 3 SHOWS GAS PIPING ABOVE ROOF. FLOOR PLAN |
| SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE |
| CLARIFY PER WPB FBC 107.2.1. |
| C. DETAIL 10 SHOWS GAS PIPING TO ABOVE ROOF. FLOOR PLAN |
| SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE |
| CLARIFY PER WPB FBC 107.2.1. |
| 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE |
| WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |