Plan Review Notes
Plan Review Notes For Permit 19050683
Permit Number 19050683
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-19 16:04:38BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19050683
 REVIEWED: JULY 19, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 401.2 FBC[CE]
 THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 -PLEASE ADJUST THE DOOR SECTION TO MEET WHAT IS
 PROVIDED IN THE PLANS. CURRENTLY THE ENERGY CALCS SHOW
 SOLID CORE DOORS ON N, E AND S SIDES.
 PLANS SHOW GLASS DOORS ON THE N AND W SIDES AND
 MULTIPLE HOLLOW METAL ON THE S SIDE.
 - ALSO, THE ROOF SECTION STATES METAL ROOF, BUT THE
 PLANS SHOW WOOD TRUSSES WITH PLYWOOD. COORDINATE THE
 PLANS WITH THE ENERGY CALCS.
  
 2) SHEET A503 DETAIL 12 SHOWS R-19 BATTS AT THE 1 5/8
 METAL FURRING. THAT DOES NOT MATCH THE ENERGY
 CALCULATION STHAT CALL FOR 6.9 AT THE MASONRY WALLS.
 ENERGY CALC AT 6.9 SEEMS TO BE THE CORRECT R VALUE.
 A) PLEASE CO-ORDINATE THE ENERGY CALS AND PLANS.
 ALSO, THERE IS A BREAK IN THERMAL ENVELOPE BETWEEN THE
 TOP OF 1 5/8 METAL FURRING AND THE ROOF SUSPENDED R39
 BATT INSULATION. PLEASE SHOW ON PLANS HOW THERMAL
 ENVELOPE IS
 B) SHOW ON PLANS HOW THERMAL ENVELOPE IS MAINTAINED.
  
 3) PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA
 FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS
 GOING TO BE.
 - DUE TO THE PROXIMITY OF THE BUILDING TO AE FLOOD ZONE
 , A BASE FLOOD ELEVATION CERTIFICATE WILL BE NEEDED TO
 DOCUMENT THAT THE FINISHED FLOOR ELEVATION MEETS THE
 BFE 12.7 NAVD PLUS 2 FOOT FREEBOARD ESTABLISHED BY THE
 CITY OF WEST PALM BEACH.
  
 4) 110.3(A)1.1 FBC[AMENDED] A FOUNDATION/FORM BOARD
 SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR
 MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB
 INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE
 BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING
 SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB
 SITE FOR REVIEW BY THE BUILDING INSPECTOR.
 PROVIDE BASE FLOOD ELEVATION(B.F.E.) IN CERTIFICATE
 WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL
 EQUIPMENT AS APPLICABLE. ALL ELEVATION CERTIFICATES
 CERTIFIED OCTOBER 5, 2017 AND LATER ARE TO UTILIZE
 NAVD88 AND INCLUDE A CONVERSION TO NGVD29.
  
 5) 602.3 TYPE III CONSTRUCTION.
 - PLEASE CONVEY THAT THIS CONSTRUCTION TYPE REQUIRES
 TWO HOUR EXTERIOR WALL AND THE EXECPTION IN NOTE A
 WOULD APPLY TO REDUSE IT TO ONE HOUR.
  
 6) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 -ADD MULTI PAGE PDF TO SUPPORTING DOCUMENT IN PROJECT
 DOX.
  
 7) [FBC 107.5][FBC 110.9][FBC R401.3][THE CIVIL PLANS
 PROVIDED ARE BASED IN NGVD 29. THE CITY OF WEST PALM
 BEACH HAS BEEN UTILZING NAVD 88.
 - PLEASE PROVIDE CIVIL PLAN ELEVATIONS IN NAVD, OR
 PROVIDE CONVERSION SO THAT ELEVATION CERTIFICATE CIVIL
 PLANS CAN BE COMPARED WITH PROPER CONVENTION.
  
 8) 1803.5.8 FBC[B] COMPACTED FILL MATERIAL. WHERE
 SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A
 GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL
 INCLUDE ALL OF THE FOLLOWING:
 - (SEE 1803.5.8 FOR REQUIREMENTS)
  
 9) 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER
 ASSEMBLIES.
 - IS THE CEILING SPACE VENTED?
  
 10) 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED
 INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE
 INSTALLED IN ACCORDANCE WITH ITEM 5.1. IN ADDITION TO
 THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW
 THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET
 INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE
 STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R
 VALUES IN TABLE 1203.3 FOR CONDENSATION CONTROL.
 - REVIEW THIS SECTION FOR AIR PERMEABLE INSULATION IN
 REGARDS TO CONDENSATION CONTROL.
  
 11) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT
 I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A
 LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND.
 SOME ITEMS ON THE LIST MAY INCLUDE: STOREFRONT, DOORS,
 ROOFING, WOOD TRUSSES.
  
 11A) SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS
 AS WELL.
 - AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE
 SPRINKLERS, LOW VOLTAGE , LANDSCAPING, PARKING LOT AND
 SITE LIGHTING
  
 12) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, STOREFRONT AND DOORS.
 - OR PUT IN THE DEFERRED SUBMITTAL LIST.
  
 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS.
 PLEASE PROVIDE FOR FLAT ROOF.
 - OR PUT IN THE DEFERRED SUBMITTAL LIST.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  