2019-07-19 16:04:38 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19050683 |
| REVIEWED: JULY 19, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 401.2 FBC[CE] |
| THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| SECTION 9.4.1.1(G) OF THE STANDARD. |
| -PLEASE ADJUST THE DOOR SECTION TO MEET WHAT IS |
| PROVIDED IN THE PLANS. CURRENTLY THE ENERGY CALCS SHOW |
| SOLID CORE DOORS ON N, E AND S SIDES. |
| PLANS SHOW GLASS DOORS ON THE N AND W SIDES AND |
| MULTIPLE HOLLOW METAL ON THE S SIDE. |
| - ALSO, THE ROOF SECTION STATES METAL ROOF, BUT THE |
| PLANS SHOW WOOD TRUSSES WITH PLYWOOD. COORDINATE THE |
| PLANS WITH THE ENERGY CALCS. |
| |
| 2) SHEET A503 DETAIL 12 SHOWS R-19 BATTS AT THE 1 5/8 |
| METAL FURRING. THAT DOES NOT MATCH THE ENERGY |
| CALCULATION STHAT CALL FOR 6.9 AT THE MASONRY WALLS. |
| ENERGY CALC AT 6.9 SEEMS TO BE THE CORRECT R VALUE. |
| A) PLEASE CO-ORDINATE THE ENERGY CALS AND PLANS. |
| ALSO, THERE IS A BREAK IN THERMAL ENVELOPE BETWEEN THE |
| TOP OF 1 5/8 METAL FURRING AND THE ROOF SUSPENDED R39 |
| BATT INSULATION. PLEASE SHOW ON PLANS HOW THERMAL |
| ENVELOPE IS |
| B) SHOW ON PLANS HOW THERMAL ENVELOPE IS MAINTAINED. |
| |
| 3) PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA |
| FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS |
| GOING TO BE. |
| - DUE TO THE PROXIMITY OF THE BUILDING TO AE FLOOD ZONE |
| , A BASE FLOOD ELEVATION CERTIFICATE WILL BE NEEDED TO |
| DOCUMENT THAT THE FINISHED FLOOR ELEVATION MEETS THE |
| BFE 12.7 NAVD PLUS 2 FOOT FREEBOARD ESTABLISHED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 4) 110.3(A)1.1 FBC[AMENDED] A FOUNDATION/FORM BOARD |
| SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR |
| MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB |
| INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE |
| BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING |
| SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB |
| SITE FOR REVIEW BY THE BUILDING INSPECTOR. |
| PROVIDE BASE FLOOD ELEVATION(B.F.E.) IN CERTIFICATE |
| WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL |
| EQUIPMENT AS APPLICABLE. ALL ELEVATION CERTIFICATES |
| CERTIFIED OCTOBER 5, 2017 AND LATER ARE TO UTILIZE |
| NAVD88 AND INCLUDE A CONVERSION TO NGVD29. |
| |
| 5) 602.3 TYPE III CONSTRUCTION. |
| - PLEASE CONVEY THAT THIS CONSTRUCTION TYPE REQUIRES |
| TWO HOUR EXTERIOR WALL AND THE EXECPTION IN NOTE A |
| WOULD APPLY TO REDUSE IT TO ONE HOUR. |
| |
| 6) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| -ADD MULTI PAGE PDF TO SUPPORTING DOCUMENT IN PROJECT |
| DOX. |
| |
| 7) [FBC 107.5][FBC 110.9][FBC R401.3][THE CIVIL PLANS |
| PROVIDED ARE BASED IN NGVD 29. THE CITY OF WEST PALM |
| BEACH HAS BEEN UTILZING NAVD 88. |
| - PLEASE PROVIDE CIVIL PLAN ELEVATIONS IN NAVD, OR |
| PROVIDE CONVERSION SO THAT ELEVATION CERTIFICATE CIVIL |
| PLANS CAN BE COMPARED WITH PROPER CONVENTION. |
| |
| 8) 1803.5.8 FBC[B] COMPACTED FILL MATERIAL. WHERE |
| SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL |
| MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A |
| GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL |
| INCLUDE ALL OF THE FOLLOWING: |
| - (SEE 1803.5.8 FOR REQUIREMENTS) |
| |
| 9) 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER |
| ASSEMBLIES. |
| - IS THE CEILING SPACE VENTED? |
| |
| 10) 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED |
| INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE |
| INSTALLED IN ACCORDANCE WITH ITEM 5.1. IN ADDITION TO |
| THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW |
| THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET |
| INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE |
| STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R |
| VALUES IN TABLE 1203.3 FOR CONDENSATION CONTROL. |
| - REVIEW THIS SECTION FOR AIR PERMEABLE INSULATION IN |
| REGARDS TO CONDENSATION CONTROL. |
| |
| 11) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE |
| PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT |
| I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A |
| LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. |
| SOME ITEMS ON THE LIST MAY INCLUDE: STOREFRONT, DOORS, |
| ROOFING, WOOD TRUSSES. |
| |
| 11A) SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS |
| AS WELL. |
| - AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE |
| SPRINKLERS, LOW VOLTAGE , LANDSCAPING, PARKING LOT AND |
| SITE LIGHTING |
| |
| 12) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| FOR WINDOWS, STOREFRONT AND DOORS. |
| - OR PUT IN THE DEFERRED SUBMITTAL LIST. |
| |
| 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. |
| PLEASE PROVIDE FOR FLAT ROOF. |
| - OR PUT IN THE DEFERRED SUBMITTAL LIST. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |