Plan Review Notes For Permit 19050677 |
Permit Number |
19050677 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-06-07 14:26:38 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | 1. OK; FBC B 107.1 THE PLANS HAVE BEEN SIGNED AND | | SEALED BY DESIGNER OF RECORD. | | 2. FAIL; FBC B 107.2.1 PROVIDE A SURVEY SHOWING THE | | STRUCTURE AND COMPLETE DRIVEWAY ON LOT INCLUDING SET | | BACK MEASUREMENTS. | | 3. FAIL; FBC B 107.1 PROVIDE THE PRODUCT APPROVAL FOR | | THE NEW WINDOW TO BE INSTALLED. | | 4. OK; FBC B 109.3 THE EVALUATION BREAKDOWN WAS | | SUBMITTED BY NEWBOLD CONSTRUCTION AND HAS BEEN ADJUSTED | | TO A VALUATION OF $9,570.00. |
|