2019-05-29 10:18:16 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. MATH IS NOT CORRECT. NEC 220; FBC RE E3602.2 |
| 2. NOTE 1 STATES THAT AT LEAST 50% OF ALL LAMPS SHALL |
| BE ENERGY EFFICIENT. CURRENT ENERGY CODE REQUIRES A |
| MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| EFFICACY LAMPS. PROVIDE CORRECTION TO NOTE. FBC EC |
| C405.1, R404.1 |
| 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. THERE IS NO |
| EVIDENCE OF THIS ON PLAN. PROVIDE CORRECTION. NEC |
| 210.11(C)(3) , FBC RE E3703.4 |
| 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |