2019-06-03 15:41:13 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE, AS WELL |
| AS PROPOSED CHANGE. NEC 215.5; WPB FBC 107.2.1 |
| 2. TO INCREASE THE SERVICE SIZE TO THE UNIT, WE WILL |
| NEED TO SEE THE EXISTING SERVICE IS ADEQUATE FOR THIS. |
| PROVIDE LOAD CALCULATION FOR ENTIRE PORTION OF SERVICE |
| THIS UNIT IS FED FROM, INCLUDE EXISTING AND NEW LOADS |
| TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, |
| 220, 408.30 |
| 3. PROVIDE ACCURATE LOAD CALCULATION, LAUNDRY WASHER |
| AND DRYER IS NOT INCLUDED. GFCI CIRCUITS FOR BATHROOMS |
| ARE NOT COUNTED AS A SMALL APPLIANCE CIRCUIT. NEC 220 |
| 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| NEC 110.10 |
| 5. PROVIDE AIC RATING OF PANEL. NEC 110.3, 110.9 |
| 6. NOTE STATES THAT 50% OF LIGHTING SHALL BE ENERGY |
| EFFICIENT. THIS IS NOT THE CURRENT CODE. PROVIDE |
| CORRECTION. FBC EC C405.1, R404.1 |
| 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |