Date |
Text |
2019-06-05 07:24:58 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19050673 |
| ADD: 4500 N. FLAGLER DR. SUITE: D24 |
| CONT: BLUE WATER VENTURES OF PALM BEACH |
| TEL: 561-339-6128 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 5, 2019 |
| ACTION: DENIED |
| |
| 1) SHEET A1 INDICATES THE REMOVAL OF FLOOR FINISHES IN |
| VARIOUS ROOMS. THE PROPOSED FLOOR PLAN INDICATES NEW |
| FLOOR FINISHES TO BE INSTALLED IN SELECTED ROOMS. THE |
| PLAN IS SILENT AS TO WHAT THE FLOOR FINISHES ARE IN |
| EACH ROOM. THE FLOOR FINISHES HAVE TO BE A KNOWN |
| ELEMENT FOR THE FLOOR SOUND INSULATION HAS TO BE TESTED |
| INSULATION AND THE FLOOR FINISH. SEE THE (3) REQUIRED |
| TEST THAT WILL NEED TO BE SUBMITTED, NOT A SALES |
| BROCHURE. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |