2019-05-15 15:21:50PLUMBING 1ST REVISION REVIEW**DENIED**
  
 1) SHT. A5.0 PROVIDE TOILET PAPER DISPENSER MEASUREMENT
 OF 7"-9" FROM THE LIP OF THE TOILET TO THE CENTER OF
 THE ROLL. FBC-ACC 604.7
  
 2) THE DOOR TO MEN'S TOILET ROOM # 211 SWINGS INTO THE
 CLEAR FLOOR SPACE OF THE LAV. NO DOOR SHALL BE
 PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE. FBC-ACC 603.2.3
  
 3) SHT. A4.0 CALLS OUT MEN'S AND WOMEN'S ADA ROOMS.
 SHEET A5.0 IN DETIL # 2,4,6,8 CALLS OUT FOR UNISEX
 TOILET ROOMS. UNISEX ROOMS ARE ONLY PERMITTED WITH THE
 OCCUPANT LOAD IS UNDER 16 WHEN 1 SINGLE RESTROOM IS
 ALLOWED TO BE UNISEX. PLEASE CORRECT LIST AS MEN'S AND
 WOMEN'S ADA MATCHING SHT. A4.0. FBC 107.2.1
  
 4) PLEASE REMOVE THE NOTE ON SHT. 2.0 THAT "EXISTING
 TOILET ROOMS COMPLY WITH ADA AND ADDITIONAL TOILETS
 ROOMS PROVIDED ARE A CONVENIENCE ONLY". WHERE TOILET
 ROOM ARE PROVIDED THEY SHALL COMPLY WITH FLORIDA
 ACCESSIBILITY. FBC-ACC 213.1
  
 5) WHERE IS THE TEMPERED WATER COMING FROM? WHAT IS THE
 OVERALL DISTANCE FROM THE SOURCE AND PROVIDE LOCATION
 OF OR ADD NOTE TO INSTALL ASSE 1070 DEVICE AT EACH LAV.
 FBC P 607.1.2
  
  