Plan Review Notes For Permit 19050639 |
Permit Number |
19050639 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-05-15 15:21:50 | PLUMBING 1ST REVISION REVIEW**DENIED** | | | | 1) SHT. A5.0 PROVIDE TOILET PAPER DISPENSER MEASUREMENT | | OF 7"-9" FROM THE LIP OF THE TOILET TO THE CENTER OF | | THE ROLL. FBC-ACC 604.7 | | | | 2) THE DOOR TO MEN'S TOILET ROOM # 211 SWINGS INTO THE | | CLEAR FLOOR SPACE OF THE LAV. NO DOOR SHALL BE | | PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OF ANY | | FIXTURE. FBC-ACC 603.2.3 | | | | 3) SHT. A4.0 CALLS OUT MEN'S AND WOMEN'S ADA ROOMS. | | SHEET A5.0 IN DETIL # 2,4,6,8 CALLS OUT FOR UNISEX | | TOILET ROOMS. UNISEX ROOMS ARE ONLY PERMITTED WITH THE | | OCCUPANT LOAD IS UNDER 16 WHEN 1 SINGLE RESTROOM IS | | ALLOWED TO BE UNISEX. PLEASE CORRECT LIST AS MEN'S AND | | WOMEN'S ADA MATCHING SHT. A4.0. FBC 107.2.1 | | | | 4) PLEASE REMOVE THE NOTE ON SHT. 2.0 THAT "EXISTING | | TOILET ROOMS COMPLY WITH ADA AND ADDITIONAL TOILETS | | ROOMS PROVIDED ARE A CONVENIENCE ONLY". WHERE TOILET | | ROOM ARE PROVIDED THEY SHALL COMPLY WITH FLORIDA | | ACCESSIBILITY. FBC-ACC 213.1 | | | | 5) WHERE IS THE TEMPERED WATER COMING FROM? WHAT IS THE | | OVERALL DISTANCE FROM THE SOURCE AND PROVIDE LOCATION | | OF OR ADD NOTE TO INSTALL ASSE 1070 DEVICE AT EACH LAV. | | FBC P 607.1.2 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] |
|