2019-05-21 13:54:03 | 1ST REVIEW: 19050604 |
| |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1.SHT. A.08 DETAIL #6 IT APPEARS THE LAVATORY IS |
| ENCROACHING INTO THE 60"X56" CLEAR FLOOR SPACE FOR THE |
| TOILET.NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. PER |
| FBC ACC 604.3.2 |
| |
| 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR. |
| |
| 3. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC |
| A) 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR |
| FLOOR OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR |
| A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND |
| TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| B)602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| C)602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT |
| OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| D)306.3.1 GENERAL. SPACE UNDER AN ELEMENT BETWEEN 9 |
| INCHES AND 27 INCHES ABOVE THE FINISH FLOOR OR GROUND |
| SHALL BE CONSIDERED KNEE CLEARANCE AND SHALL COMPLY |
| WITH 306.3. |
| E)306.2.1 GENERAL. SPACE UNDER AN ELEMENT BETWEEN THE |
| FINISH FLOOR OR GROUND AND 9 INCHES ABOVE THE FINISH |
| FLOOR OR GROUND SHALL BE CONSIDERED TOE CLEARANCE AND |
| SHALL COMPLY WITH 306.2. |
| |
| 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE,PER FBC ACC 609.4 |
| |
| 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH |
| CONTROLS. FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| SIDE OF THE WATER CLOSET EXCEPT IN AMBULATORY |
| ACCESSIBLE COMPARTMENTS COMPLYING WITH 604.8.2 |
| |
| 6.THE BREAK ROOM SINKS SHALL COMPLY WITH FBC ACC 606.2 |
| CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH |
| 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND |
| TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 7. IN THE NEW BATHROOM THERE IS A PLUMBING FIXTURE THAT |
| THE ARCHITECTURAL SHEETS ARE CALLING A MOP SINK THE |
| PLUMBING SHEET IS CALLING IT A SHOWER PLEASE CLARIFY IF |
| IT IS A SHOWER IT SHALL COMPLY WITH FBC ACC 608.2.1 , |
| 608.3.1 , 608.5.1 , 610.3 |
| |
| 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 9. BACKFLOW IS REQUIRED FOR THE ICE MACHINE IN |
| REFRIGERATOR IF ONE PROVIDED. PER FBC PL 608.3 |
| |
| 10. THE WATER FOUNTAIN ON THE 2ND FLOOR SHALL CONNECT |
| TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. |
| PER FBC PL 912.1 |
| |
| 11. SHT. A.08 DETAIL #2 SHOWS A MOP SINK BUILT IN PLACE |
| WITH LATICRETE HYDROBAN WATER PROOFING THE PLUMBING |
| SCHEDULE IS LISTING P-5 PRE FAB SHOWER PLEASE |
| CLARIFY.PER WPB AMEND TO FBC 107.2.1 |
| |
| . |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |